Super Free Match Series
④ The following table for the torque required to tighten the nuts.
Table 5
Thickness of
Pipe diameter
copper tube
Φ6.35 mm
≥0.8 mm
Φ9.52 mm
≥0.8 mm
Φ12.7 mm
≥0.8 mm
Φ15.9 mm
≥1.0 mm
Φ19.05 mm
≥1.0 mm
-------------------------------------------------------------------------------------------------------------------------
Caution!
During the connection of the indoor unit and BU module to the refrigerant pipe, never pull any
joints of the indoor unit and the BU module by force; otherwise the capillary pipe or other pipe
may crack, which then would result in leakage.
The refrigerant pipe should be supported by brackets, that is, don't let the unit withstand the
weight of it.
For the Super Free Match system, each pipe should be labeled to tell which system it belongs to
avoid mistaken inaccurate piping.
-------------------------------------------------------------------------------------------------------------------------
6.5
Connection of Refrigerant Pipe
Tightening
torque
15~30 N· m
35~40 N· m
45~50 N· m
60~65 N· m
70~75 N· m
12
Fig. 14