Ocultar thumbs Ver también para VFD 400:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 26
EN 
 
Turn On/Off 
 
Press the switch of the UPS continuously for 1 second and the UPS turns into its normal state 
(the green light is on and the beeper is off) after it performs a self‐diagnosis (the beeper and 
the red and green indicator lights are on) for several seconds. At this time, user may turn on the 
PC and other loads. Press the switch of the UPS continuously for 1 second to turn off the UPS. 
Note:  
For  the  convenience  of  maintenance,  please  turn  on  the  UPS  first  before  turning  on 
the PC and the other loads, and turn off the UPS after the loads are turned off. 
At  ordinary  times,  we  recommend  to  remain  the  UPS  on  with  the  battery  charging 
(even if the loads are turned off), which is benefit to the maintenance of the battery. 
 
 
3. Trouble Shooting 
 
Symptom 
Possible Cause 
1. Missing battery 
No LED display  
2. Battery defect 
on the front panel 
3. Power switch is not pressed 
1. Overload of the UPS 
2. Battery voltage is too low 
When power 
failure, backup 
3. Battery defect due to high 
time is short. 
temperature operation 
environment, or improper 
operation to battery. 
1. Circuit breaker is broken. 
Mains  normal  but 
LED is flashing. 
2. Power cord is loose. 
 
If any abnormal situations occur that are not listed above, please call service people immediately. 
 
Remedy 
1. Charge battery up to 8 hours 
2.  Replace  with  the  same  type 
of  battery 
3. Press power switch again 
1. Remove some noncritical load
2. Charge battery 8 hours or 
more 
3. Replace with the same type  
of battery 
1. Reset the circuit breaker. 
2. Reconnect the power cord 
properly. 
Tabla de contenido
loading

Este manual también es adecuado para:

Vfd 600Vfd 1000

Tabla de contenido