Installer Settings - Prostat PRS6110 Manual Del Instalacion

Ocultar thumbs Ver también para PRS6110:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

4 Installer Settings

The Installer Settings must be properly configured in order for this thermostat to operate correctly. The
Installer Settings are menu driven. The portion of these settings that do not apply to your setup will be
skipped. These settings are indicated below with comments. More detail on each setting follows this table.
1. Press and hold down the RETURN and
buttons for 3 seconds.
2. Release both buttons and the first
installer setting will be displayed.
3. Change settings as required using the
or
buttons.
4. Press NEXT (HOLD) or BACK (PROG) to
move to the next or previous setting,
press RETURN to exit.
NOTE: Shaded areas below do not apply to the PRS6110.
No. Installer Setting
(
Notes follow this table)
1
Residential or
or Commercial Profile
2
Programming Mode
[note 1]
3
Clock Format
4
Temperature Scale
5
Auto Changeover
6
System Type
Installer Manual
INSTRUCTIONS
BACK
NEXT
Factory
Default
RES
7 PROG
12 HR
F DEG
oF AUTO
11CONV
Setting
Comments
Options
(More information follows this table)
RES
Select for Residential profile
COMM
Select for Commercial profile
7 PROG
Select for 7 day programming mode
52 PROG
Select for 5-2 day programming mode
NO PROG
Select for non-programmable mode
12 HR
Select for 12 hour clock
24 HR
Select for 24 hour clock
F DEG
Select for Fahrenheit display
C DEG
Select for Celsius display
oF AUTO
Disables Auto Changeover mode
ON AUTO
Enables Auto Changeover mode
11CONV
Select for 1H/1C Conventional system
22CONV
Select for 2H/2C Conventional system
11HP
Select for 1H/1C Heat Pump system
21 HP
Select for 2H/1C Heat Pump system (PRS6110)
22HP
Select for 2H/2C Heat Pump system
32HP
Select for 3H/2C Heat Pump system
1HD
Select for Heat Only Hydronic system
11HD
Select for Hydronic Heat/1C system
8
INSTRUCTIONS
BACK
NEXT
Tabla de contenido
loading

Este manual también es adecuado para:

Prs6320

Tabla de contenido