BIP LD2-T_ _ _-03-S75
Inductive Positioning System
4
Installation and connection (continued)
4.2
Electrical Connection
2
4
1
3
Fig. 4-4:
Pin assignment of S75 connector
(view from above on connector of BIP)
Pin
Wire color
1
Brown
2
–
3
Blue
4
Black
Unassigned leads that are not used can be connected to the GND on
1)
the controller side but not to the shield.
Tab. 4-2:
Pin assignment of S75 connector
4.3
Cable routing
Defined ground!
The BIP and the control cabinet must be at the
same ground potential.
Magnetic fields
The BIP operates according to the eddy current principle.
It is important to maintain adequate distance between the
BIP and strong, external magnetic fields.
Cable routing
Do not route the cable between the BIP, controller, and
power supply near high voltage cables (inductive stray
noise is possible).
Inductive stray noise from AC harmonics (e.g. from phase
angle controls) are especially critical and the cable shield
offers very little protection against this.
Cable length
Cable length max. 20 m. Longer cables may be used if
their construction, shielding and routing prevent noise
interference.
8
english
Signal
L+ (18...30 V)
Not used
1)
L– (GND)
C/Q (communication line)