6.3 Fault and Warning Messages

6.3.1 Error messages

Errors which occur are shown in coded form by an error number in the LED display on the front panel. All error
messages result in the BTB/RTO contact being opened, and the output stage of the amplifier being switched off
(motor loses all torque). If a motor-holding brake is installed, it will be activated.
Number Designation
E/S/A/P Status Messages
. . .
Status Message
-
Status Message
F01
Heat sink temperature Heat sink temperature too high limit is set by manufacturer to 80°
F02
Overvoltage
F03
Following error
F04
Feedback
F05
Undervoltage
F06
Motor temperature
F07
Internal voltage supply Internal amplifier supply voltages are out of tolerance
F08
Overspeed
F09
EEPROM
F10
Flash-EPROM
F11
Brake (motor)
F12
Motor phase
F13
Internal temperature
F14
Output stage
F15
I²t max.
F16
Supply BTB/RTO
F17
A/D converter
F18
Brake
F19
Supply phase
F20
Slot fault
F21
Handling error
F22
Earth short circuit
F23
CAN-bus off
F24
Warning
F25
Commutation error
F26
Limit switch
F27
AS
F28
External Trajectory
F29
Slot Fault
F30
Emergency timeout
F31
Macro
F32
System Error
More information to the messages can be found in the ASCII Object Reference
ERRCODE. Hints for removal can be found in section "Trouble-Shooting" of the online help.
182
Kollmorgen | wiki-kollmorgen.eu | April 2016
Explanation
Status messages, no error, see p.
Updating the startup configuration
Programming mode
Overvoltage in DC bus link limit depends on the electrical supply voltage
Message from the position controller
Cable break, short-circuit, short to ground
Undervoltage in DC bus link limit is set by manufacturer to 100V
Motor temperature too high or temp. sensor defect, limit is fixed to 145°C
Motor over-revs, speed is too high
Checksum error
Checksum error
Cable break, short-circuit, short to ground
Motor phase missing (cable break or similar)
Internal temperature too high
Fault in the power output stage
I²t maximum value exceeded
2 or 3 phases missing in the mains supply feed
Error in the analog-digital conversion, normally caused by extreme elec-
tromagnetic interferences.
Brake circuit faulty or incorrect setting
A phase is missing in the mains supply power feed (can be switched off for
2-phase operation)
Slot error (hardware fault on expansion card)
Software error on the expansion card
For 40/70 amps type only, short-circuit between motor phase and ground
Severe CAN bus communication error
Warning is displayed as fault
Commutation error
Homing error (machine has driven onto hardware limit switch)
Error with -AS- , input for AS-Enable and ENABLE set at the same time
Ext. position profile generator created a step, that exceeds the max. value
depends on expansion card, see online help
Timeout emergency stop
Macro program error
system software not responding correctly
(online help
), see parameter