Mounting to junction box with mounting plate:
The EOPC-100 can be mounted to a pre-installed junction box
using the mounting plate that is provided. The mounting plate
works on single or double gang J-boxes.
1. Attach mounting plate to junction box with the provided
screws.
2. Snap the sensor onto the mounting plate using the
threaded screw.
Junction box
Mounting plate
Snap
Screws
EOPC-100
Mounting directly to junction box:
The EOPC-100 can also be mounted directly to a junction box
using the provided screws.
1. Use two machine screws (included with the J-Box) to
attach the sensor to the mounting tabs on the J-Box.
2. Align the sensor in the J-Box so that the mounting screw
tabs on the J-Box match the key holes on the sensor's rear
housing.
3. Slide sensor onto the junction box.
Junction box
EOPC-100
WARNING: Do Not Install To Cover a Junction Box Having Class
1, 3 or Power and Lighting Circuits.
SENSOR MOUNTING
Screws
Mounting to wood or non metal surfaces:
The EOPC-100 can be mounted to any flat surface, or placed
directly on the surface using the reversable mounting disc
provided. One side of the disc is backed with foam tape for
mounting to non-metal surfaces; the reverse side provides a
super-magnet for mounting to metal.
1. Use the pull tab to release the mounting disc.
2. Snap the mounting disc into insert on back of sensor, tape
end face up.
3. Attach the sensor to the desired location with the tape.
Reversable mounting disc
Mounting
disc pull tab
Pull tab to release mounting disc
Foam tape
(reversable
mounting
disc)
Through ceiling tile:
The EOPC-100 can be mounted through the ceiling tile using the
mounting plate that is provided.
1. Attach mounting plate to ceiling tile as shown.
2. Drill hole in ceiling.
3. Line up threaded screw with hole in ceiling tile.
4. Snap the sensor onto the mounting plate through the hole
in ceiling tile using the threaded screw.
4
One side is a super-
magnet for mounting
to metal, reverse side
acts as foam tape for
mounting to non-metal
surfaces
Ceiling
Sensor Mount
Adhere to
surface
Mounting plate
Line up threaded screw
with hole in ceiling tile
and screw in place
EOPC-100
Ceiling tile