LEGRAND WattStopper EOPC-100 Instrucciones página 3

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

IMPORTANT NOTE: THE MAXIMUM NUMBER OF OCCUPANCY
SENSORS (EOPC-100) AND WALL SWITCHES (EOSW-1XX) THAT
CAN BE PAIRED TOGETHER IS TEN. WHEN THE MAXIMUM NUMBER
OF DEVICES HAVE REACHED THE LIMIT, THE GREEN PAIRING
"P" LED WILL FLASH RAPIDLY TO INDICATE THAT IT IS FULL.
*It is recommended that pairing of devices be done prior to installing ceiling sensor.
Step 1 Enter Pairing Mode
Press and Hold "Pairing" Button "P" on Receiver for 3 seconds then release:
• "Pairing" LED blinks 2 times/ second to confirm pairing mode For EOSW-101/EOSW-111
• Load 1 turns ON and is ready to be paired
• Button 1 LED is Solid ON For EOSW-102/EOSW-112
• Load 1 & 2 turn ON and are ready to be paired
• Button 1 & 2 LED are Solid ON
Step 2 Selecting a Specific Load to Pair (EOSW-102/EOSW-112)
*By default, both loads turn On at the same time in Pairing Mode. If both loads are to be
controlled by Occupancy Sensor than skip this step.
Tap the "Pairing" Button "P" once while in pairing mode:
• Load 2 turns OFF and Load 1 remains ON
• Load 1 is now active and ready to be paired to selected transmitters
• Load 1 LED is Solid ON
Tap the "Pairing" Button "P" once again while in pairing mode:
• Load 1 turns OFF and Load 2 tturns ON
• Load 2 is now active and ready to be paired to selected transmitters
• Load 2 LED is Solid ON
Tap the "Pairing" Button "P" a third time while in pairing mode:
• Load 1 and Load 2 turn ON again, indicating both loads are ready to be paired.
Step 3 Pair Occupancy Sensor to Receiver
* While the receiver is in pairing mode and the load you want to pair the sensor with is ON:
Tap the "Pair"Button on the Occupancy Sensor
• The selected load(s) will flash OFF/ON for visual pairing confirmation
EOPC-100 Button Locations
IMPORTANT NOTE: YOU WILL HAVE ONLY 30 SECONDS
TO COMPLETE THE PAIRING MODE OPERATION
Step 4 Exit "Pairing" Mode on Receiver
Once a device is paired with the receiver the receiver will automatically exit "pairing" mode.
• The receiver will also exit "pairing" mode if no device is paired to it within 30 seconds.
• Pressing and holding the "Pairing" button "P" for 3 seconds also exits the pairing process.
NOTE: To pair additional devices to the same load, repeat Step 1 to re-enter "Pairing" mode.
Step 5 Verify Occupancy Sensor is "Paired" with the Receiver(s)
Tap the "Pairing" button "P" on the EOPC-100 while in normal operating mode.
• The load(s) will turn OFF, and will turn ON immediately (and remain On) if motion is detected.
Press and hold the Pairing button "P" on the receiver for about 10 seconds. The green LEDs will flash 3 times indicating un-pairing has
occurred.
PAIRING OF SENSOR TO RECEIVERS
Pairing Button
TO "UN-PAIR" ALL CONNECTED DEVICES
3
EOSW-101
"Load Status"
legrand
Blue LED
Pairing
Button
EOSW-102
"Load Status"
legrand
Blue LED
Pairing
Button
EOSW-102
"Load 1 Status"
legrand
Blue LED ON
Pairing
Button
EOSW-102
"Load 1 Status"
legrand
Blue LED OFF
Pairing
Button
"Load 2 Status"
Blue LED On
Tabla de contenido
loading