6.8. CONNECTING THE UNIT TO THE WATER NETWORK

- Maximum pressure : 31,62 bar
- Maximum temperature: 150ºC
• For heat exchangers with threaded connections, secure the coil manifold with the appropria-
te tool when tightening the threads. This will prevent the force from being transmitted to the
manifold, which can damage it.
• The following table gives a list of the types of thread for each humidifi er:
UTBS-2 (2, 4 or 6 -pipes)
UTBS-3 (2, 4 or 6 -pipes)
UTBS-5 (2, 4 or 6 -pipes)
UTBS-8 (2, 4 or 6 -pipes)
• The water coils must run counter to the fl ow of air to provide the correct performance. This
means that the fl uid inlet must be connected on the manifold located on the air outlet side,
and the fl uid outlet must be connected on the manifold situated on the air intake side, as
shown in the following illustrations:
MODEL
THREAD
35x1,5 ( 1"3/8)
35x1,5 ( 1"3/8)
35x1,5 ( 1"3/8)
42x1,5 (1"5/8)
42