U
SE
FUNCTION
Time interval for the
Battery test
automatic battery test
Alarm threshold
Selects the overload
for maximum
load
Selects the level of
Display
brightness of the LCD
brightness
Selects the mode of
Sound alarm
operation of the sound
Selects the permitted
range for the input
Input frequency
switchover to bypass
tolerance
synchronization
Selects the permitted
Bypass voltage
voltage range for
thresholds
switchover to bypass
Selects the permitted
Bypass voltage
voltage range for ECO
thresholds for
mode operation
ECO
Selects the sensitivity
Sensitivity of
of intervention during
intervention for
operation in ECO
ECO mode
Power supply of the
Load power
load on bypass with
supply in stand-
UPS switched of
by
(stand-by status)
Selects the mode for
Bypass operation
use of the bypass line
56
DESCRIPTION
PREDEFINED
40 hours
Disabled
user limit
Maximum
Reduced
alarm
ADVANCED FUNCTIONS
frequency for
± 5%
and for output
Low:
High: 264V
Low:
High: 253V
Normal
mode
Disabled
(load NOT
powered)
Normal
POSSIBLE CONFIGURATIONS
Disabled
1 ÷ 1000 in steps of 1 hour
Disabled
0 ÷ 103 in steps of 1%
Minimum ÷ Maximum in 20 steps
Normal
Reduced: does not sound for
momentary intervention of the bypass
± 0.25%
± 0.5%
± 0.75%
± 1 ÷ ±10 in steps of 1%
180V
Low :
180 ÷ 200 in steps of 1V
High:
250 ÷ 264 in steps of 1V
200V
Low: 180 ÷ 220 in steps of 1V
High:
240 ÷ 264 in steps of 1V
Low
Normal
High
Disabled (not powered)
Enabled (powered)
Normal
Disabled with input/output
synchronization
Disabled without input/output
synchronization
MODE