Technical Specifications; Power Data; Electronics/General Data - Weq CFW500 Serie Manual Del Usuario

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Technical Specifications

8 TECHNICAL SPECIFICATIONS

8.1 POWER DATA

Power Supply:
Tolerance: -15 % to +10 %.
Frequency: 50/60 Hz (48 Hz to 62 Hz).
Phase imbalance: ≤ 3 % of the rated phase-to-phase input voltage.
Overvoltage according to Category III (EN 61010/UL 508C).
Transient voltage according to Category III.
Maximum of 10 connections (power up cycles - ON/OFF) per hour (1 every 6 minutes).
Typical efficiency: ≥ 97 %.
For further information about the technical specifications, refer to
SPECIFICATIONS on page

8.2 ELECTRONICS/GENERAL DATA

CONTROL
METHOD
OUTPUT
FREQUENCY
PERFORMANCE
V/f CONTROL
VECTOR
CONTROL
(V V W )
INPUTS
ANALOG
(*)
DIGITAL
OUTPUTS
ANALOG
(*)
40 | CFW500
141.
Table 8.1: Electronics/general data
Type of control:
- V/f (Scalar).
- V V W: Voltage vector control.
PWM SVM (Space Vector Modulation).
0 to 500 Hz, resolution of 0.015 Hz.
Speed regulation: 1 % of the rated speed (with slip compensation).
Speed variation range: 1:20.
Speed regulation: 1 % of the rated speed.
Speed variation range: 1:30.
1 insulated input. Levels: (0 to 10) V or (0 a 20) mA or (4 to 20) mA.
Linearity error ≤ 0.25 %.
Impedance: 100 kΩ for voltage input, 500 Ω for current input.
Programmable functions.
Maximum voltage permitted in the input: 30 Vdc.
4 insulated inputs.
Programmable functions:
- active high (PNP): maximum low level of 15 Vdc.
- active low (NPN): maximum low level of 5 Vdc.
Maximum input voltage of 30 Vdc.
Input current: 4.5 mA.
Maximum input current: 5.5 mA.
1 insulated output. Levels (0 to 10) V or (0 to 20) mA or (4 to 20) mA.
Linearity error ≤ 0.25 %.
Programmable functions.
RL ≥ 10 kΩ (0 to 10 V) or RL ≤ 500 Ω (0 to 20 mA / 4 to 20 mA).
APPENDIX B – TECHNICAL
minimum high level of 20 Vdc.
minimum high level of 9 Vdc.
Tabla de contenido
loading

Tabla de contenido