Ribind K500 Manual Del Usaurio página 31

Ocultar thumbs Ver también para K500:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

red DL1 LED will stop flashing.
6 - Reposition DIP 1 to OFF and DIP 2 to OFF.
7 - You have completed the procedure
PROCEDURE FOR DELETING ALL RADIO CODES USED ONLY FOR COMPLETE OPENING
You can only delete the codes if the gate is closed.
1 - Position DIP 1 to ON and then DIP 2 to ON.
2 - The red programming DL1 LED will flash ON and OFF, one second on each, for 10 seconds.
3 - Press and hold the PROG button for 5 seconds. The green DL2 LED will flash twice to
confirm that the stored codes have been deleted.
4 - The red programming DL1 LED remains active and you can programme new codes as
shown above if required.
5 - Reposition DIP 1 to OFF and DIP 2 to OFF.
6 - You have completed the procedure.
HOW TO CHECK IF THE MEMORY IS FULL FOR RADIO CODES USED ONLY FOR
COMPLETE OPENING
You can only check the memory if the gate is closed.
1 - Position DIP 1 to ON and then DIP 2 to ON.
2 - The green DL2 LED will flash 6 times if the memory is full (30 codes have been stored).
3 - After this, the DL1 programming LED will remain active for 10 seconds, so that you can
delete all codes if required.
4 - Reposition DIP 1 to OFF and DIP 2 to OFF.
5 - You have completed the procedure
POINT G
- PROGRAMMING RADIO CODES FOR PEDESTRIAN OPENING
(UP TO 30 CODES - ONLY FOR CRX MODELS)
You can only programme the codes if the gate is closed.
1 - Position DIP 1 to ON and then DIP 3 to ON.
2 - The red programming DL1 LED will flash ON and OFF, one second on each, for 10 seconds.
3 - Press the remote control button (normally channel B) within the 10 seconds proscribed. If
the remote control has been correctly programmed, the DL2 LED (green) will flash once.
4 - The code programming time resets automatically so that you can programme the next
remote control.
5 - To finish programming, let 10 seconds pass and then press the PROG. button briefly. The
red DL1 LED will stop flashing.
6 - Reposition DIP 1 to OFF and DIP 3 to OFF.
N.B: IF THE DL1 LED CONTINUES TO FLASH RAPIDLY, THIS MEANS THAT DIP 1 IS
STILL POSITIONED TO ON AND ANY MANOEUVRE HAS BEEN DELETED.
7 - You have completed the procedure.
PROCEDURE FOR DELETING ALL RADIO CODES USED ONLY FOR COMPLETE OPENING
You can only delete the codes if the gate is closed.
1 - Position DIP 1 to ON and then DIP 3 to ON.
2 - The red programming DL1 LED will flash ON and OFF, one second on each, for 10 seconds.
3 - Press and hold the PROG button for 5 seconds. The green DL2 LED will flash twice to
confirm that the stored codes have been deleted.
4 - The red programming DL1 LED remains active and you can programme new codes as
shown above if required.
5 - Reposition DIP 1 to OFF and DIP 3 to OFF.
6 - You have completed the procedure.
HOW TO CHECK IF THE MEMORY IS FULL FOR RADIO CODES USED ONLY FOR
COMPLETE OPENING
You can only check the memory if the gate is closed.
1 - Position DIP 1 to ON and then DIP 3 to ON.
2 - The green DL2 LED will flash 6 times if the memory is full (30 codes have been stored).
3 - After this, the DL1 programming LED will remain active for 10 seconds, so that you can
delete all codes if required.
4 - Reposition DIP 1 to OFF and DIP 3 to OFF.
5 - You have completed the procedure.
FUNCTIONING OF CONTROL ACCESSORIES
ATTENTION: ONLY IMPULSIVE COMMANDS HAVE TO BE CONNECTED.
Make sure that any other type of command accessories (e.g. mass detectors)
used on the installation are set in the IMPULSIVE mode, otherwise, the gate
will be operated even without the protection of the safety devices.
STEP BY STEP or AUTOMATIC commands
(K BUTT button, PED BUTT button, RADIO REMOTE button)
DIP 6 - ON
The K BUTT, the PED BUTT button, the RADIO REMOTE buttons perform the cyclic command
open-stop-close-open-stop-etc.
DIP 6 - OFF The K BUTT, the PED BUTT button, the RADIO REMOTE buttons perform:
- the open command, if pressed with the gate completely closed
- the close command, if pressed with the gate completely opened
- no effect, if pressed during the gate opening
- the gate re-open, if pressed while the gate is closing
The K BUTT opens the gate completely, whereas the PED BUTT opens the gate partially as
described in Point D.
CLOCK FUNCTION
If you want the Clock Function must request K2007 with firmware 10 NOUP.
ATTENTION: A CLOCK CONNECTED TO K2007 with fw 05 or more ACTIVATES THE AUTOMATIC
MOVEMENT OF THE GATE WITHOUT HAVING THE PROTECTION OF THE SAFETY DEVICES!
The Clock Function is useful during rush hours, when traffic is heavy and the flow is
slow (e.g. entrance/exit of employees, emergencies in residential areas or car parks and,
temporarily, for removal vans) and it's necessary to keep the gate opened.
CLOCK FUNCTION APPLICATION
It is necessary to request a K2007 control panel with firmware 10 NOUP.
Select the automatic functioning DIP 6 OFF.
It can be done by connecting a switch and/or a daily/weekly clock either in parallel to
the K BUTT button or instead of the K BUTT button. When the control board receives
this command, the gate will open and by keeping this contact closed for all the time of
the gate opening, the Clock Function is automatically activated. In fact, once reached
the open position, the gate will remain opened and all of the control board functions
are blocked. Only when K BUTT contact is released, the control board functions are
re-activated and the Automatic Closing restarts (if enabled) doing the countdown to the
gate closing.
PEDESTRIAN command (PED BUTT - COM)
This command is useful to open the gate partially, just enough, for example, to permit a
pedestrian crossing. In fact, the Pedestrian command (see Point E) is carried out only by
opening the gate just enough for a pedestrian to pass, as described into the Point E procedure.
From the Pedestrian opening position the Automatic Closing can be enabled or disabled with
DIP3. From the Pedestrian opening position, the gate can be completely opened by the OPEN
or by the K BUTT button or by the RADIO button.
AUTOMATIC CLOSING (from the COMPLETE open position)
The Automatic Closing from the complete open position can be enabled turning ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes (see Point D).
AUTOMATIC CLOSING (from the PEDESTRIAN open position)
The Automatic Closing from the pedestrian open position can be enabled turning ON the DIP3.
The maximum gap of time that can be programmed is 5 minutes (see Point E).
FUNCTIONING OF SAFETY ACCESSORIES
PHOTOCELL (PHOT - COM)
In case the switch DIP4 is in the OFF position, the photocells are active both in gate opening
and in gate closing. In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will stop and will restart opening when the obstacle is
removed
- while the gate is still, it will not move neither in opening nor in closing.
In case of the switch DIP4 is in the ON position, the photocells are active only in gate closing.
In this configuration, if an obstacle cuts the photocell beam:
- while the gate is closing, the gate will open
- while the gate is opening, the gate will continue open
- while the gate is still, it will open if a open command is request, it will remain still if a close
command is request.
The photocell input (PHOT - COM) is a NORMALLY CLOSED contact.
In case there are more couple of photocells, the contacts from all the photocell receivers must
be connected in series.
In case the photocells are not installed, this contact must be short circuited with a wire jump
(from PHOT to COM) to permit the gate to operate.
SAFETY STRIP (EDGE - COM)
If it intervenes during opening, it inverts the movement and closes for 2 seconds and then
stops.
If it intervenes during closing, it inverts the movement and opens for 2 seconds and then stops.
If the safety strip remains engaged (NO contact), no automatic movement is allowed.
In case the safety strip is not installed, this contact must be short circuited with a wire jump
(from EDGE to COM) to permit the gate to operate.
PAY ATTENTION: it is highly recommended to check safety-strips operation at least every 6
months.
SAFETY STRIP ALARM
After the inversion given by the intervention of the safety edge, the gate stops in alarm mode
and this is signaled by the blinker on for 1 minute and by the buzzer on for 5 minutes.
During or after the minute of alarm, the normal gate operations can be restored by pressing
any push button.
31
G
B
Tabla de contenido
loading

Tabla de contenido