Siemens GEB1 Serie Instrucciones De Montaje página 9

Actuador de acción rotativa
Ocultar thumbs Ver también para GEB1 Serie:
de
Kabelbezeichnungen
en
Wire designations
Siemens Building Technologies
Anschluss
Code Nr.
Antriebe
G
1
AC 24 V
G0
2
Y1
6
Y2
7
Y
8
U
9
Antriebe
N
4
AC 230 V
Y1
6
Y2
7
Hilfsschalter
Q11
S1
Q12
S2
Q14
S3
Q21
S4
Q22
S5
Q24
S6
Rückführ-
a
P1
potentimeter
b
P2
c
P3
Connection
Code No.
AC 24 V
G
1
Actuators
G0
2
Y1
6
Y2
7
Y
8
U
9
AC 230 V
N
4
Actuators
Y1
6
Y2
7
Auxiliary switch Q11
S1
Q12
S2
Q14
S3
Q21
S4
Q22
S5
Q24
S6
Feedback
a
P1
potentiometer
b
P2
c
P3
74 319 0109 0 e
Kabel
Bedeutung
Farbe
Akürzung
rot
RD
System Potential AC 24 V
schwarz
BK
Systemnull
violett
VT
Stellsignal AC 0 V "Uhrzeigersinn"
orange
OG
Stellsignal AC 0 V "Gegenuhrzeigersinn"
grau
GY
Stellsignal DC 0...10 V, 0...35 V
rosa
PK
Stellungsanzeige DC 0...10 V
blau
BU
Nullleiter
schwarz
BK
Stellsignal AC 230 V, Uhrzeigersinn
weiss
WH
Stellsignal AC 230 V,Gegenuhrzeigersinn
grau/rot
GYRD
Schalter A Eingang
grau/blau
GYBU
Schalter A Ruhekontakt
grau/rosa
GYPK
Schalter A Schliesskontakt
schwarz/rot
BKRD
Schalter B Eingang
schwarz/blau BKBU
Schalter B Ruhekontakt
schwarz/rosa BKPK
Schalter B Schliesskontakt
weiss/rot
WHRD
Potentiometer 0...100 % (P1-P2)
weiss/blau
WHBU
Potentiometer Abgriff
weiss/rosa
WHPK
Potentiometer 100...0 % (P3-P2)
Cable
Meaning
Color
Abbreviation
red
RD
System potential AC 24 V
black
BK
System neutral
purple
VT
Actuating signal AC 0 V "clockwise"
orange
OG
Actuating signal AC 0 V "anticlockwise"
gray
GY
Actuating signal DC 0...10 V, 0...35 V
pink
PK
Position indication DC 0...10 V
blue
BU
Neutral
black
BK
Actuating signal AC 230 V, "clockwise"
white
WH
Actuating signal AC 230 V, "anticlockwise"
gray/red
GYRD
Switch A input
gray/blue
GYBU
Switch A normally closed contact
gray/pink
GYPK
Switch A normally open contact
black/red
BKRD
Switch B input
black/blue
BKBU
Switch B normally closed contact
black/pink
BKPK
Switch B normally open contact
white/red
WHRD
Potentiometer 0...100 % (P1-P2)
white/blue
WHBU
Potentiometer pick-off
white/pink
WHPK
Potentiometer 100...0 % (P3-P2)
M4621
10-01-2013
9/12
loading