KCER-01MF
Multifunction Tester
5.2.7 Using the VOLTAGE Function
WARNING!
Do not use on a circuit whose voltage either L-L or L-N exceeds 550V Measuring the Voltage and Frequency
Figure 19. Standby screen for the Voltage and Frequency
1. Connect the test lead input terminal
2. Turn the rotary switch to the VOLTAGE position
Figure 20 Screen while measuring Voltage and Frequency
Do not attempt to measure when the input voltage is above 500V a.c.
Value at the top right hand corner represents the Voltage, and the value in the right hand centre represents the
frequency
The display will appear without the TEST button operated.
5.2.8 Using the Phase Sequence Function
Determining the Phase Sequence
31