The Hydrovar-Watercooled contains electronic safety devices which switch off the control element
in the event of a fault, whereby the motor has zero current but remains energized and comes to a
halt. The motor can also be halted by mechanical blocking. If it is electronically switched off the
motor is disconnected from the mains voltage through the electronics of the Hydrovar-Watercooled
but is not potential-free in the circuit.
In addition voltage fluctuations, especially power failures can cause the system to switch off itself.
Repair of faults can cause the motor to start up again!
The system may only be put into operation when it has been earthened. In addition, equipotential bonding of all
pipes must be ensured.
The operating instructions must be read, understood and followed by the operating personnel. We point out that we
accept no liability for damage and operating disorders which are the result of non-compliance with the operating
instructions.
Transportation, Handling:
Check the Hydrovar-Watercooled immediately upon delivery/receipt of dispatch for damage or missing parts. If
any damage is visible, inform your distributor within 8 days from the delivery date.
The unit must be transported carefully and by competent personnel.
Avoid serious impacts.
Attention: Dispose of all packing materials in accordance with local regulations
2
Technical Data
HYDROVAR Watercooled
Type
HVW 1.07
0,75 kW
System pressure:
Motor cable length:
Overload:
Cooling:
Liquid temperature:
Ambient temperature:
Storage temperature:
Humidity:
Air pollution:
Altitude:
Class of protection:
Temperature: Liquid temperature depends on the ambient temperature
Power supply
Voltage
220-240 V +/- 15%
0 - 6 bar
max. 20 Meter
max. 20 %
through handled liquid (Water, Service water)
max. +50° C
see diagram below
0° C ... +50° C
see diagram below
-25° C ... +55° C (+70° C during max. 24 hours)
RH max. 50% at 40° C, unlimited
RH max. 90% at 20° C, max. 30 days per year
75% average per year (Class F)
Condensation is not permitted !
The air may contain dry dust as found in workshops where there is no
excessive quantity of dust due to machines.
Excessive amounts of dust, acids, corrosive gases, salts etc. are not permitted
max. 1000m above sea level
At sites over 1000 m above sea level, the maximum output power is derated by
1% for every additional 100m.
If the installation site is higher than 2000 m above sea level, please contact
your local distributor.
IP 55
Max. nominal
Frequency
motor current
48-62 Hz
4,2 A
13
Weight
[kg]
3,3