TR
TR
OUBLESHOO
OUBLESHOO
TR
TR
TROUBLESHOO
OUBLESHOOTING
OUBLESHOO
Reset Operation
Reset Operation
Reset Operation
Reset Operation
Reset Operation
Note
Note
Note: When thermostat is reset, installer configuration menu settings and programming will reset to factory settings.
Note
Note
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by removing
the wires from terminals R R R R R and C C C C C (do not short them together) and removing batteries for 2 minutes. After resetting the thermostat, replace
the wires and batteries. If the thermostat has been reset and still does not function correctly contact your heating/cooling service person or
place of purchase.
Note
Note: Be sure to review the installer configuration menu settings.
Note
Note
Note
To reset the programming, clock and configuration settings, press
go blank and then all segments will be displayed momentarily.
Symptom
Symptom
Symptom
Symptom
Symptom
No Heat/No Cool/No Fan
No Heat/No Cool/No Fan
No Heat/No Cool/No Fan
No Heat/No Cool/No Fan
No Heat/No Cool/No Fan
(common problems)
(common problems)
(common problems)
(common problems)
(common problems)
No Heat
No Heat
No Heat
No Heat
No Heat
No Cool
No Cool
No Cool
No Cool
No Cool
Heat, Cool or Fan
Heat, Cool or Fan
Heat, Cool or Fan
Heat, Cool or Fan
Heat, Cool or Fan
Runs Constantly
Runs Constantly
Runs Constantly
Runs Constantly
Runs Constantly
Thermostat Setting &
Thermostat Setting &
Thermostat Setting &
Thermostat Setting &
Thermostat Setting &
Thermostat Thermometer
Thermostat Thermometer
Thermostat Thermometer
Thermostat Thermometer
Thermostat Thermometer
Disagree
Disagree
Disagree
Disagree
Disagree
Furnace (Air Conditioner)
Furnace (Air Conditioner)
Furnace (Air Conditioner)
Furnace (Air Conditioner)
Furnace (Air Conditioner)
Cycles Too Fast or Too Slow
Cycles Too Fast or Too Slow
Cycles Too Fast or Too Slow
Cycles Too Fast or Too Slow
Cycles Too Fast or Too Slow
(narrow or wide
(narrow or wide
(narrow or wide
(narrow or wide
(narrow or wide
temperature swing)
temperature swing)
temperature swing)
temperature swing)
temperature swing)
White-Rodgers is a division
of Emerson Electric Co.
The Emerson logo is a
trademark and service mark
of Emerson Electric Co.
TING
TING
TING
TING
Possible Cause
Possible Cause
Possible Cause
Possible Cause
Possible Cause
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or
panel loose or not properly installed.
4. Loose connection to thermostat or system.
1. Pilot light not lit.
2. Furnace Lock-Out Condition. Heat
may also be intermittent.
3. Heating system requires service or
thermostat requires replacement.
1. Cooling system requires service or
thermostat requires replacement.
1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in heat/cool/fan system.
4. FAN Switch set to Fan ON
ON.
ON
ON
ON
1. Thermostat thermometer setting
requires adjustment.
1. The location of the thermostat and/or
the size of the Heating System may
be influencing the cycle rate.
HOMEOWNER HELP LINE
HOMEOWNER HELP LINE
HOMEOWNER HELP LINE: 1-800-284-2925
HOMEOWNER HELP LINE
HOMEOWNER HELP LINE
St. Louis, Missouri
St. Louis, Missouri
St. Louis, Missouri
St. Louis, Missouri
St. Louis, Missouri
www.white-rodgers.com
www.white-rodgers.com
www.white-rodgers.com
www.white-rodgers.com
www.white-rodgers.com
and
and the FAN button simultaneously. The thermostat should
Corrective Action
Corrective Action
Corrective Action
Corrective Action
Corrective Action
Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage safety
interlock or door switch.
Tighten connections.
Re-light pilot.
Many furnaces have safety devices that shut down when a
lock-out condition occurs. If the heat works intermittently
contact the furnace manufacturer or local HVAC service
person for assistance.
Diagnostic: Set SYSTEM Switch to HEAT
Diagnostic
Diagnostic
Diagnostic
Diagnostic
setpoint above room temperature. Within a few seconds
the thermostat should make a soft click sound. This sound
usually indicates the thermostat is operating properly. If
the thermostat does not click, try the reset operation listed
above. If the thermostat does not click after being reset
contact your heating and cooling service person or place
of purchase for a replacement. If the thermostat clicks,
contact the furnace manufacturer or a HVAC service
person to verify the heating is operating correctly.
Same as diagnostic for No Heat condition except set the
thermostat to COOL
COOL
COOL and lower the setpoint below the
COOL
COOL
room temperature. There may be up to a five minute delay
before the thermostat clicks in Cooling.
Check each wire connection to verify they are not shorted
or touching together. No bare wire should stick out from
under terminal block. Try resetting the thermostat as
described above. If the condition persists the manufacturer
of your system or service person can instruct you on how
to test the Heat/Cool system for correct operation. If the
system operates correctly, replace the thermostat.
The thermometer can be adjusted +/- 4 degrees. See
Temperature Display Adjustment in the Configuration
Menu section.
Digital thermostats provide precise control and cycle faster
than older mechanical models. The system turns on and
off more frequently but runs for a shorter time so there is
no increase in energy use. If you would like an increased
cycle time, choose SL
SL
SL for slow cycle in the Configuration
SL
SL
menu, step 6 (heat), 7 (cool) or 8 (heat pump). If an
acceptable cycle rate is not achieved, contact a local
HVAC service person for additional suggestions.
: 1-800-284-2925
: 1-800-284-2925
: 1-800-284-2925
: 1-800-284-2925
HEAT
HEAT and raise the
HEAT
HEAT