BASICS
TESTING and MAINTENANCE
Unit Status Indications
The "TEST" button illuminates to indicate the following conditions:
Indication:
Status:
Off
Unit is off
Flashing green
Unit is in Emergency operation or Test
Solid amber
Battery is charging
Solid green
Battery is fully charged
Manual test, battery not fully charged (SDRT
Flashing R / G
only)
1x red flashing
Battery failure (SDRT only)
2x red flashing
Lamp assembly failure (SDRT only)
3x red flashing
Charger / electronics failure
Flashing R/Amber Unable to charge
Solid Red
Battery is disconnected
Normal indicators
Load Learn Feature has been executed see
with short Red
Load-Learning Feature on previous page for
flash every 2
description
seconds
Remote
Test
(SDRT
separately)
Units with the self-diagnostics/remote test feature allows manual
test activation using a laser pointer. Aim the laser beam straight
onto the circular area labeled near the "TEST" button for a few
moments to activate a 60-second test. (See also "Manual testing")
A test in progress may be cancelled by aiming the beam at the
test area again. NOTE: The remote tester should not be used to
initiate the load learning feature.
"
"
TEST
button