ODCOM-R
HOLDING REGISTERS
Data type
1
Device slave address unsigned int.
2
Modbus baud rate
unsigned int.
3
Modbus parity mode unsigned int.
4
Device type
unsigned int.
5
HW version
unsigned int.
6
FW version
unsigned int.
7—8
Modbus network
9
Bus termination
unsigned int.
(NBT)
Modbus registers
10
unsigned int.
reset
Minimum
11
signed int.
temperature range
Maximum
12
signed int.
temperature range
Minimum
13
signed int.
temperature alert
Maximum
14
signed int.
temperature alert
15—18
Minimum relative
19
unsigned int.
humidity range
Maximum relative
20
unsigned int.
humidity range
Minimum relative
21
unsigned int.
humidity alert
Maximum relative
unsigned int.
22
humidity alert
23—26
27
Minimum CO range
unsigned int.
28
Maximum CO range
unsigned int.
29
Minimum CO alert
unsigned int.
30
Maximum CO alert
unsigned int.
31
Minimum NO
range
unsigned int.
2
32
Maximum NO
range
unsigned int.
2
33
unsigned int.
Minimum NO
alert
2
34
Maximum NO
alert
unsigned int.
2
35
Active level
unsigned int.
36
Standby level
unsigned int.
37—80
Para una información más detallada respecto a la comunicación Modbus, véase:
MIW-ODCOM-R-ES-000 - 29 / 07 / 2019
TRANSMISOR MULTIFUNCIONAL
PARA CONDICIONES EXTREMAS
Description
Modbus device address
Modbus communication baud rate
Parity check mode
Device type (Read only)
Hardware version of the device (Read
only)
Firmware version of the device (Read
only)
Reserved, return 0
Set device as end device of the line / or
not by connecting NBT
Resets Modbus Holding registers to
default values. When finished this
register is automatically reset to '0'
Minimum value of temperature range,
cannot be set higher than maximum
temperature range minus 5°C
Maximum value of temperature range,
cannot be set less than minimum
temperature range plus 5°C
Minimum temperature alarm value
Maximum temperature alarm value
Reserved, return 0
Minimum value of relative humidity
range, cannot be set higher than
maximum relative humidity range
minus 5%
Maximum value of relative humidity
range, cannot be set less than
minimum relative humidity range plus
5%
Minimum relative humidity alarm value
Maximum relative humidity alarm
value
Reserved, return 0
Minimum value of CO, cannot be set
higher than maximum value minus
1ppm
Maximum value of CO, cannot be set
lower than minimum value plus 1ppm
Minimum CO alarm value
Maximum CO alarm value
Minimum value of NO
, cannot be set
2
higher than max value minus 0,1 ppm
Maximum value of NO
, cannot be set
2
lower than min value plus 0,1 ppm
Minimum NO
alarm value
2
Maximum NO
alarm value
2
The ambient light level above which
'Active' is indicated in input register 6
The ambient light level below which
'Standby' is indicated in input register
6
Reserved, return 0
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
www.sentera.eu
volver al índice
Data
Default
1—247
0—6
0—2
ODCOM-R = 1103
XXXX
XXXX
0—1
0 – 1
-300 – (Max. range - 50)
(Min. range + 50) – 700
Min. temperature range – Max.
temperature alarm
Min. temperature alarm – Max.
temperature range
0 – (Max. range - 50)
(Min. range + 50) – 1000
Min. relative humidity range –
Max. relative humidity alarm
Min. relative humidity alarm –
Max. relative humidity range
0 – (Max. range – 10)
(Min. range +10) - 1000
Min. CO range – Max. CO alarm
Min. CO alarm – Max. CO range
0 – (Max. range -10)
(Min. range + 10) - 1000
Min. NO
range – Max. NO
2
2
alarm
Min. NO
alarm – Max. NO
2
2
range
0—32000
0—32000
Values
1
0 =
1 =
2 =
2
3 =
4 =
5 =
115.200
6 =
230.400
0 =
1
1 =
2 =
0x0100 =
HW version 1.00
0x0100 =
FW version 1.00
0 =
NBT disconnected
0
1 =
NBT connected
0 =
0
Reset Modbus Registers
1 =
300
100 =
700
700=
-300
100 =
700
700=
0
200 =
20,0 % rH
1000
1000 =
100 % rH
0
200 =
20,0 % rH
1000
1000 =
100 % rH
0
100=
100 ppm
1000
100=
100 ppm
0
0 =
100
200=
200 ppm
0
0 =
1000
100=
0
0 =
100
100=
100
100 =
10
10=
4.800
9.600
19.200
38.400
57.600
8N1
8E1
8O1
Idle
10,0°C
70,0°C
10,0°C
70,0°C
0 ppm
0 ppm
1 ppm
0 ppm
1 ppm
100 lx
10 lx
9 - 10