COMPROBACIÓN DEL MONTAJE EFECTUADO

MAPAS DEL REGISTRO MODBUS

INPUT REGISTERS
1
Actual temperature value
2
Temperature output value
3
Temperature alert flag
Temperature range limit
4
flag
5
Temperature sensor state
6—9
Actual relative humidity
10
value
Relative humidity output
11
value
12
Relative humidity alert flag
Relative humidity range
13
limit flag
14
Humidity sensor state
15
Calculated dew point
16—25
26
CO level
27
CO Output value
28
CO alert flag
29
CO range limit flag
30
CO Sensor state
31
NO
level
2
32
NO
Output value
2
33
NO
alert flag
2
34
NO
range limit flag
2
35
NO
Sensor state
2
41
Ambient light intensity
36—40
42
Active / Standby
43
Ambient light sensor state
44—50
MIW-ODCOM-R-ES-000 - 29 / 07 / 2019
TRANSMISOR MULTIFUNCIONAL
PARA CONDICIONES EXTREMAS
Si su dispositivo no funciona correctamente, compruebe las conexiones.
Data type
Description
signed int.
Actual temperature level
unsigned int.
Output value according to temperature
Flag indicates that measured Temperature is outside
set alert values. Set to '1' when the measured value
unsigned int.
is outside temperature alert values defined by
holding registers 13 and 14
Flag indicates that measured temperature is outside
set range limit values. Set to '1' when the measured
unsigned int.
temperature is outside limit range values defined by
holding registers 11 and 12
Flag that shows if the communication with
unsigned int.
temperature sensor is lost
Reserved, return 0
unsigned int.
Actual relative humidity level
unsigned int.
Output value according to relative humidity
Flag indicates that measured Relative humidity
is outside set alert values. Set to '1' when the
unsigned int.
measured value is outside relative humidity alert
values defined by holding registers 17 and 18
Flag indicates that measured Relative humidity is
outside set range limit values. Set to '1' when the
unsigned int.
measured relative humidity is outside limit range
values defined by holding registers 15 and 16
Flag that shows if communication with humidity
unsigned int.
sensor is lost
signed int.
Calculated dew point
Reserved, return 0
unsigned int.
Relevant CO level
unsigned int.
Output value according to CO
Flag indicates that measured CO level is outside set
alert values. Set to '1' when the measured value is
unsigned int.
outside the CO values defined by holding registers
25 and 26
Flag indicates that measured CO is outside set
range limit values. Set to '1' when the measured CO
unsigned int.
is outside limit range values set defined by holding
registers 23 and 24
Flag that shows if the communication with the CO
unsigned int.
sensor is lost
unsigned int.
Relevant NO
level
2
unsigned int.
Output value according to NO
Flag indicates that measured NO
set alert values. Set to '1' when the measured
unsigned int.
value is outside the NO
registers 29 and 30
Flag indicates that measured NO
range limit values. Set to '1' when the measured NO
unsigned int.
is outside limit range values set defined by holding
registers 27 and 28
Flag that shows if the communication with the NO
unsigned int.
sensor is lost
unsigned int.
Measured ambient light intensity
Reserved, return 0
Active or Standby indication according the Active /
Standby light level defined by holding registers 31
unsigned int.
and 32. If the measured light level is between the
two levels the indication is 0 (Low intensity)
Flag that shows if communication with ambient
unsigned int.
light sensor is lost
Reserved, return 0
Data
-300—700
0—1000
0—1000
0—1000
-700—700
0 —1000
0 —1000
0 – 1000
0 – 1.000
2
level is outside
2
values defined by holding
2
is outside set
2
2
2
0—32 000
www.sentera.eu
volver al índice
Values
0 = Temperature measurement OK
0—1
1 = Temperature measurement too low/high
0 = Temperature range OK
0—1
1 = Temperature range too low/high
0—1
0 = Relative humidity measurement OK
0—1
1 = Relative humidity measurement too low/high
0 = Relative humidity range OK
0—1
1 = Relative humidity range too low/high
0—1
0 = CO measurement OK
0—1
1 = CO measurement too low/high
0—1
1 = CO range too low/high
0—1
0 = NO
0—1
1 = NO
measurement too low/high
2
0 – 1
1 = NO2 range too low/high
0—1
0 = Low light intensity
0—2
0—1
500 = 50,0°C
0 = 0 %
1.000 = 100 %
0 = No
1 = Yes
1.000 = 100,0 % rH
0 = 0 %
1.000 = 100 %
0 = No
1 = Yes
200 = 20,0°C
100 = 100 ppm
0 = 0 %
1.000 = 100 %
0 = CO range OK
0 = No
1 = Yes
100 = 1 ppm
0 = 0 %
1.000 = 100 %
measurement OK
2
0 = NO
range OK
2
0 = No
1 = Yes
1000 = 1000 lux
1 = Active
2 = Standby
0 = No
1 = Yes
8 - 10