Dynamic current limiter
Intended for generators, the AC voltage is being generated by means of a static inverter (so-
called 'inverter' generators). In these generators, rpm is down-controlled if the load is low: this
reduces noise, fuel consumption and pollution. A disadvantage is that the output voltage will
drop severely or even completely fail in the event of a sudden load increase. More load can
only be supplied after the engine is up to speed.
If this setting is 'on', the MultiPlus will start supplying extra power at a low generator output level
and gradually allow the generator to supply more, until the set current limit is reached. This
allows the generator engine to get up to speed.
This setting is also often used for 'classic' generators that respond slowly to sudden load
variation.
WeakAC
Strong distortion of the input voltage can result in the charger hardly operating or not operating
at all. If WeakAC is set, the charger will also accept a strongly distorted voltage, at the cost of
greater distortion of the input current.
Recommendation: Turn WeakAC on if the charger is hardly charging or not charging at all
(which is quite rare!). Also turn on the dynamic current limiter simultaneously and reduce the
maximum charging current to prevent overloading the generator if necessary.
Not adjustable with DIP switches.
BoostFactor
Change this setting only after consulting with Victron Energy or with an engineer trained by
Victron Energy!
Not adjustable with DIP switches.
Programmable relay
By default, the programmable relay is set as an alarm relay, i.e. the relay will de-energise in the
event of an alarm or a pre-alarm (inverter almost too hot, ripple on the input almost too high,
battery voltage almost too low).
Not adjustable with DIP switches.
Near the connection terminals an LED illuminates when the relay is activated.
VEConfigure
With VEConfigure software the relay can also be programmed for other purposes, for example
to provide a generator starting signal.