Cleaning (suitable for both mounting situations)
1.
7
Close the
inlet valve
2.
3
Open the
drain
to release the system pressure.
3.
Open the heating system refill valve, to generate a pressure
contrary to the normal water flow, to proceed with the
backwashing of the filter.
4.
5
Extract the
magnet
impurities will settle because they are no longer attracted by
the
magnet
.
5.
Leave the water flow until it is clear.
It is not possible to establish a time within which the
cleaning of the filter is completed, since this depends
i
on the amount of impurities present in the plant that have
been intercepted by the filter. It is therefore recommended
to make sure that the outlet water from the drain is
perfectly clean before proceeding to close it.
TECNOGAS manuale di installazione | setup manual | manuel d'instalation | manual de instalación | manual de instalare | manual de instalação
.
by unscrewing it from its
housing
ENGLISH
6.
Once cleaning is completed, close the heating system refill
valve, then proceed to close the
to the end of stroke .
7.
Screw back the
8.
Slowly reopen the
9.
6
. All
Make sure that the heating system is working at the proper
pressure and, if needed, operate on the heating system refill valve.
This cleaning procedure is recommended every 3-4
months, although the time frame may depend on the
amount of impurities in the system. In the case of highly
contaminated systems, moreover, it may be necessary
i
to clean also the mechanical filter of the magnetic dirt
separator. In this case, it is necessary to unscrew the
main ring nut
remove the filter and clean it. After cleaning, you must
remount the filter following the mounting instructions at
the
Internal mount
3
, screwing the cap
drain
5
6
magnet
on its
housing
.
7
inlet valve
.
8
, remove the upper part of the filter,
paragraph.
13