Indicator leds are described:
LEDS
ALARM
Test Mode
DISABLE
GENERAL FAULT
SUPPLY FAULT
SYSTEM FAULT
SOUNDER FAULT
COM
KEYBOARD
ACCESS
POWER SUPPLY
BATTERY
ACT SOUNDER
SILENCE
SOUNDER
ALARM
Fault / Test
/Disable
SLEEPING MODE
FABRICANTE DE PRODUCTOS CONTRA INCENDIOS– FIRE PROTECTION MANUFACTURER
C/ Compositor Wagner, 8 – P.I. Can Jardí - 08191 RUBÍ (Barcelona) ESPAÑA.
Conventional Control Panel
IRON02/04
LED
color
Fire Alarm due to activation of manual call point (MPC) or
A
detector.
Red
► Fixed
Zone or zones in Test Mode.
B
Amber
► Fixed At least a zone in test mode.
Zone or zones disable.
C
Amber
► Fixed At least a zone disable.
System Fault
D
Amber
► Fixed
General power supply Fault.
► Fixed Fault 110~230VAC input, 30V and Sounders output.
E
Amber
► Blinking Without batteries.
CPU fault
F
Amber
► Fixed Control panel is not operating.
General Sounder output condition.
► Fixed Open line.
Amber
G
► Blinking Short-circui
H
Access level to keyboard´s control panel
► Off Level 1.
I
Amber
► Fixed Level 2. Activate by microswitch permanently
► Blinking Level 2. Activate by keys during 30 seconds.
System operating through 110~230 V/AC power supply.
J
Green
► Fixed
System operating under batteries.
Green
► Fixed
K
► Fixed General sounder relays on. Panel is working without
delay in general sounder relays.
N
Amber
►Blinking General sounder relays delay activated.
► Fixed General outputs sounders permanently stopped.
O
► Blinking General outputs sounders stopped until new zone
Amber
alarm.
Alarm zone
► Fixed Alarm activated by MPC.
Red
P
► Blinking Alarm activated by detector.
Test/Fault/Disable zone.
► Fixed Disable zone.
Q
Amber
► Blinking Short-circuit fault / Open line fault / Test Mode.
► Blinking Battery, General fault and Power supply fault.
Amber
Panel is in hibernation when it does not have power Supply
110/220V and batteries are under 21V.