Isolation class
Dimensions (W x H x D)
Weight
N, L,
+V, -V
BAT-, BAT+
Terminal type
RTH, FAULT, NTC
STATUS
SERIAL
Signalling
The LED indicators
[H]
signal the presence of the mains voltage
on the input terminals and the proper operating capacity of the
switching power-supply unit and its batteries.
The fault signal can be obtained through the <STATUS= input
via the two open-collector outputs <OC1= and <OC2=.
Signalling
OFF
Green LED
Switching power-
(DL1)
supply unit off
Yellow LED
Mains operating
(DL2)
properly
Yellow LED
Batteries ope-
(DL3)
rating properly
Operating pro-
Output OC1
perly
Mains operating
Output OC2
properly
Removal of the jumper from the Earth fault signalling connector
[I]
deactivates the Earth fault check.
If this appliance is used with a control panel all the obligatory sta-
tus and fault signals must be provided for and made available.
Installation
IPS24060G must be installed inside a fireproof enclosure (e.g.
the control panel metal case).
[J]
Using the mounting holes
Connect the mains wiring to the input terminal board
Attention!
This appliance must be earthed.
Using the plastic cable band, bunch the mains wires and
fasten them close to the mains wire entry on the switching
power-supply unit.
The cables used for the wiring of the product must have an
adequate section and comply with the IEC 60332-1-2 or IEC
60332-2-2 standards.
For an installation that meets standard requirements, it is
necessary to fit a suitable sectioning device (bipolar) and pro-
tection on the electrical-wiring upstream of the switching
power-supply unit in accordance with the laws in force
(DM37/08).
The output voltage can be drawn from either terminals
-V=), or from the connector
The output connector is also has <FAULT= and <RTH= terminals
which are reserved for connection to Inim Electronics control
panels.
If you are installing a ProbeTH thermal probe, connect it to con-
[E]
nector
.
Attach the thermal probe to one of the batteries in such a way as
to achieve an optimal level of thermal conductivity.
4
I
138 x 42 x 87 mm
450 g
(EN IEC 62368-1)
ES3, PS3
ES1, PS2
ES1, PS2
ES1, PS1
ES1, PS2
ES1, PS1
Blinking
ON
fast
Switching power-
Overheated
supply unit operating
Mains operating fault Earth fault
Battery fault
/
Switching power-
/
supply unit fault
Mains operating fault
/
, secure the device into its housing.
[D]
(<+V, -V=).
Manuale d'istruzioni / Instruction manual / Manual de instrucciones / Notice d9instructions - 130
Note
The backup batteries of the equipment power supply are
not included. The installer must use only valve regulated
lead-acid batteries (VRLA) for stationary use, compliant with
IEC 60896-21 and IEC 60896-22 standards.
The battery casing must have V-2 flame rating or higher.
If this appliance is used with a fire detection control panel, it
is obligatory to fit it with a thermal probe.
Installation in fire detection control panels
1.
Connect the mains wiring to the power supply input
terminal board.
2.
Locate the batteries inside the panel enclosure.
3.
Using the battery wire [A1] , connect the batteries toge-
ther.
4.
Connect the battery wire to the terminals of the bat-
[F]
teries [B1] .
5.
Connect the battery wire connector [C1] to the con-
nector on the power supply module.
slow
Attention!
Output
overload
Ensure that connector polarity is correct.
/
6.
Connect the thermal probe to the connector
on the power supply module.
/
Using a strip of strongly-adhesive insulating tape [E1] ,
7.
/
attach the thermal probe to one of the batteries, in
such a way as to a provide optimized heat-transfer
/
measurements.
Maintenance
The following maintenance operations must be performed regu-
larly:
Check that all wiring and connections are intact.
l
Check that the appliance is operating properly.
l
Check the battery efficiency.
l
Note
[A]
.
These maintenance operations must be performed by qua-
lified persons only.
About this manual
Manual code: DCMIIN4AIPS24060G
Revision: 130
Copyright: the information contained in this document is the sole property of Inim
Electronics S.r.l. No part may be copied without written authorization from Inim
Electronics S.r.l.. All rights reserved.
Manufacturer's details
Manufacturer: Inim Electronics S.r.l.
Production plant: Centobuchi, via Dei Lavoratori 10
63076 Monteprandone (AP), Italy
Tel: +39 0735 705007
Fax: +39 0735 734912
[C]
(<+V,
Web: www.inim.it
The persons authorized by the manufacturer to repair or replace the parts of this
system, hold authorization to work on Inim Electronics brand devices only.
Disposal of the product
Informative notice regarding the disposal of electrical and electronic
equipment (applicable in countries with differentiated waste col-
lection systems)
The crossed-out bin symbol on the equipment or on its packaging indi-
cates that the product must be disposed of correctly at the end of its
working life and should never be disposed of together with general hou-
sehold waste. The user, therefore, must take the equipment that has reached the
[E]
, [D1]