Comelit 45TRA100 Manual Tecnico página 8

Módulo expansor inalámbrico de alarma de incendios direccionable con aislador incorporado
Idiomas disponibles
  • ES

Idiomas disponibles

1. General Description
45TRA100 is an addressable wireless expander module
designed for operation with 41CPE118 addressable
fire alarm panel. 45TRA100 is powered directly by the
loop line and can be controlled via the communication
protocol. 45TRA100 has a built-in isolator module.
45TRA100 communicates with Comelit series wireless
devices enrolled to its configuration. The wireless devices
are automatically recognized from the fire panel and are
set in consecutive addresses after the set address of
the expander module. Up to 32 wireless devices can be
enrolled to a specific expander, forming a linear network.
Up to 5 45TRA100 wireless expander modules can be
connected to a single 41CPE118 fire alarm control panel.
45TRA100 is mounted in a compact plastic enclosure
box suitable for wall mounting. The information of the
status of the enrolled wireless devices is presented on a
LCD text display.
A dipole SMA type antenna is supplied with the expander
module to ensure wide covering range and stable
communication with the enrolled wireless devices.
2. Functional Features
• Loop powered
• Built-in isolator module
• Up to 5 wireless expanders to LogiFire 41CPE118
addressable panel
• Up to 32 Comelit series wireless devices enrolled to an
expander module
• Dipole antenna, SMA connector type
• Event messages for wireless device status: low battery,
tamper, lost device
• Menu for reviewing the signal strength of the enrolled
devices
• LCD display, dot matrix 16x2
• Multilanguage menus
• Standards applied: EN 54-18; EN 54-17; EN 54-25
3. Technical Specifications
Loop Characteristics:
Operating voltage 17-30 VDC
Nominal consumption,
LCD display ON
Nominal consumption,
LCD display OFF
Max. consumption, LCD display
Max. consumption,
LCD display OFF
Radio frequency 868MHz
Communication type Bidirectional
Communication protocol Comelit Wireless
Radio signal modulation type GFSK
Number of frequency channels 6 pair channels
Radiated power ≤ 25 mW
Receiver category (EN300-220-1) 1.5
Max. connected wireless
expanders to 41CPE118 panel/
building
Max. enrolled wireless devices to
an expander module
Communication range with
Comelit wireless devices
(open space*)
* Depends on system/control panel
capacity and building structure
Trace attenuation > -90dBm
8
12mA@29 VDC
9mA@29 VDC
17mA@16 VDC
ON
13mA@16 VDC
5
32
1500m
Antenna:
Type Dipole antenna
Frequency 866-870MHz, Center
Impedance 50Ω
Type of Radiation Omni-directional
Gain 2 dBi
Connector type SMA Male (Swivel)
Dimensions 242x12.5mm
Operation temperature -10°C to +55°C
Related humidity resistance
(no condensation)
Enclosure box:
Material ABS
Dimensions 191x125x60mm
Color White RAL 9016 / grey RAL
Protection IP40
Weight (with mounted PCB
and antenna)
4. Installation Place and Mounting
It is strongly recommended to design the Comelit
wireless system in advance on paper, before starting the
installation.
The 45TRA100 expander module should be installed at
2-2.5m above the floor level.
Attention: Avoid installation of the 45TRA100 module
and the wireless devices near to:
• Power lines or other high voltage equipment withlarge
electric consumption.
• Big metal structures - cabinets, pending ceilings, thick
concrete walls. Note that, the quality of the signal
strength is reduced with 80%, and sometimes with
100% (full reflection) in premises with metal walls or
surfaces.
• Fluorescent lamps and lighting fixtures.
• Wi/Fi Routers, wireless telephone stations, computers
and network cabling.
5. System Topology
Consult the full manual available on the pro.comelitgroup.
com website and also accessible scanning the QR code
at the end of the manual.
6. PCB Elements
Consult the full manual available on the pro.comelitgroup.
com website and also accessible scanning the QR code
at the end of the manual.
7. Connection to Loop Line
45TRA100 is connected and powered directly from
LogiFire 41CPE118 loop line. The module is equipped
with a built-in isolator module, which can be used or not,
according the requirements of the fire alarm installation.
Attention: The connection to the
loop line of the wireless expander
module must be done with
switched off main and back-up
power supply of 41CPE118 fire
alarm panel!
The module is equipped with 5-position plug terminal
for easy connection to the loop line. To connect the loop
wires just pick up the plug to dismount it from the PCB
868Mhz
(93±3)%@ 40°С
7045
~ 180g
loading