STEINEL DALI64 KNX-S Manual De Instrucciones página 22

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 30
DALI Gateway DALI64 KNX-S, DALI Gateway DALI128 KNX-S
4
Information for electrically skilled persons
4.1
Mounting and electrical connection
DANGER!
Electric shock when live parts are touched.
Electric shocks can be fatal.
Always disconnect device before carrying out work on it. For this, switch off all cor-
responding circuit breakers, secure against being switched on again and check that
there is no voltage. Cover up adjacent live parts.
Mount device
Mount device on DIN rail.
Connect device
Control cable: appropriate type, cross-section and routing for the specifications for
230 V cables. DALI and mains voltage wires can be run together in a cable, e.g.
NYM 5x1.5 mm².
The DALI control voltage is a functional extra-low voltage (FELV). When in-
stalling, perform the installation in such a way that when an area is disconnec-
ted, the lines carrying both the DALI and also the mains voltage are discon-
nected.
If multiple circuit breakers supply dangerous voltages to the device or load,
couple the circuit breakers or label them with a warning to ensure tripping.
DALI participants from some manufacturers have expanded functions and can
be controlled, for example, via mains voltage on the DALI connection. When
existing DALI installations are refitted, remove all corresponding operator con-
trols.
Connect device as shown in the connection example (see figure 3)
82406608
8 / 14
23.01.2024
loading

Este manual también es adecuado para:

Dali128 knx-s089207089214