Pulse mode (except DIM)
If the dial is set to
anti-clockwise), the unit is in
pulse mode, i.e. the output is
switched ON for approx. 2 sec.
IQ-Modus
Turned fully clockwise: The
stay-ON time is self-learning
and adjusts dynamically to user
behaviour.
COM 2
Potentiometer 7.
Stay-ON time for switching output 2 HVAC
• Setting 1 min. – 2 hr.
Potentiometer 8.
Switch-ON delay for switching output 2 HVAC
• Setting 0 sec. – 10 min.
• Turned fully clockwise:
Room surveillance
• Turned fully anticlockwise:
0 sec. (OFF)
Potentiometer 15.
Basic light level (DIM version)
Provides basic illumination for
the selected stay-ON time when
ambient light falls below the
selected light-level threshold that
is set. This can be dimmed to
10 % of maximum light intensity.
As soon as a person enters the
scene, the detector switches
either to 100 % light intensity
(constant-lighting controller OFF)
10. Reach adjustment
Potentiometer 9.
The reach required (response
threshold) is infinitely variable.
• US 360 / DualTech
at least 2 x 2 m – 6 x 6 m
presence
(fully
(e.g. for stairwell lighting timer).
Afterwards, the sensor does not
react to movement for approx. 8
sec. Day mode is the only mode
The optimum time cycle is de-
termined by means of a learning
algorithm.
• Turned fully clockwise: max
Turning the potentiometer to the
"Surveillance" setting reduces
the sensitivity of the "Presence"
switching output.
The contact only closes on de-
tecting a pronounced movement,
signalising with a high degree
or adjusts to the preselected light
level (constant-lighting controller
ON). When no movement is
being detected, the detector
dims back to basic light level
after the stay-ON time expires.
This is switched OFF when
stay-ON time (1 min. – 30 min.)
has expired or the daylight com-
ponent is sufficient to exceed
• Single US / Dual US
at least 3 x 3 m – 10 x 3 m
in each direction
- 27 -
possible here because of dazzle
by light from external sources.
The shortest time is 5 min., the
longest 20 min.
• Turned fully anti-clockwise: min
of certainty that persons are
present.
The stay-ON time remains
active. The switch-ON delay is
inactivated.
the selected level of brightness.
In the ON setting, the detector
switches basic light level ON
and OFF as soon as the level
of light falls below the light-level
threshold.
Turned fully anticlockwise =
minimum reach
Turned fully clockwise
(factory setting) = maximum reach