Kit Components
The retrofit connection kit for installing and
activating the flood sensor includes the items
shown below. If any item is missing, speak with
your account representative about ordering
code 88009419.
A. Flood sensor with mounting bolts
C. 24V DC power adapter
Requirements
• #2 Phillips screwdriver
• 120VAC, 60Hz, GFI-protected electrical outlet
(for kit power adapter), or power source
ranging from 12V to 24V
• Wire stripper
Install the Flood Sensor and Activation Module
Attach the flood sensor and the activation module to the backflow relief valve. The activation module
receives a signal from the flood sensor when a discharge is detected. If the discharge meets the
conditions of a qualifying event, the normally open contact is closed to provide a signal to the BMS
input terminal.
Custom Flood Sensor Settings
The default settings on the activation module for detecting discharge are suitable
for the assembly series. However, the DIP switches can customized for a different
wet threshold and time delay. Scan the QR code for more information.
1. Remove the bolts from the flood sensor.
NOTICE
• The connection kit is suitable for installation on the specified
valve series only.
• When installing an air gap, attach the air gap brackets directly
to the flood sensor.
B. Activation module with an 8' 4-conductor cable
D. Ground wire
2. Position the two halves of the sensor on the relief valve.
2