1.
Visually inspect that the charging light is illuminated
monthly.
2.
Test the emergency operation of the fixture monthly for
a minimum of 30 seconds. Perform the test by pressing
the test button / indicator light for 30 seconds or aiming
a laser pointer at the clear test button. The LED load
should operate at the rated output.
(Note: The laser test will not trigger if the ambient light
is too high. The light must be switched off in fixtures
where the test button is in close proximity to the light, or
the test will need to be triggered mechanically)
3.
Conduct a 90-minute discharge test annually by
disconnecting the unswitched power. The LED load
should operate at the rated output for at least 90
minutes.
4.
Keep written records of testing.
Refer any service requirements indicated by these checks
to qualified personnel.