Installation Instructions – CBRK Emergency Battery Packs
ii.
(a) Drill diameter 9/16" hole in the LED Panel (X)
for installation of Test Switch (F) on the grey
highlighted area.
(b) If there is no space in existing Retrofit Kit housing
to install Retrofit kit Panel with Flex/ conduit,
it is necessary to remove flex/ conduit before
installation of panel. To remove flex conduit,
unscrew the flex retaining screws (Y) and slide
flex/ Conduit (Z) and then remove it.
(c) Also, Trim wire length as needed to fit.
Drill a hole at dist.
of 1.15" from
panel vertical
edge shown and
hole center in high-
lighted space
Figure 3 - Drilling 9/16" diameter hole for test switch
installation on backside of fixture  
iii. Install Test Switch as shown in Figure 4.
(F) Test Switch Position
Figure 4 - Test switch installation on backside of fixture
4
COOPER LIGHTING SOLUTIONS
(Z)
(Y)
IB519148EN
Installation instructions
Alternative Option for Mounting
If Test Switch F-(1) component in Fig 1. has to be
i.
mounted someplace other than back of fixture
(as shown in Figs 3 & 4), mount the Test Button /
Indicator Light / Laser Input on a tile or a different
place such that the indicator light is visible once
the fixture is installed. Proper mounting is required
for accessibility and functionality of the laser
input testing feature and testing of EZ key battery
disconnect.
Wire the LED load, AC driver, and AC power as noted in
2.
the block diagram below.
Block diagram of wiring for EBPLED
Outside of fixture color is BLK
Power for AC Driver WHT/BLK
Outside of fixture color is BLU
Unswitched 120-277VAC
L
50/50 Hz BLK/ORG
EBPLED
Outside of fixture color is WHT
N
120-277VAC Neutral WHT
L
N
Operation
When AC power is permanently applied to the blue wire
of the fixture, remove the EZ key and store it for later use.
When AC Power is applied, the charging indicator light
is illuminated, indicating the battery is being charged.
When the power fails, the emergency ballast automatically
switches to emergency power, operating its LED load at the
rated output for at least 90 minutes.
Note: The battery is not fully charged until 24 hours after the
AC power is applied.
Maintenance
Although no routine maintenance is required to keep the
emergency LED driver functional, it should be
checked periodically to verify proper operation. Follow any
applicable local or national codes. The following schedule is
the minimum required to meet NFPA 101 standards:
Test Button/
Indicator Light/
Laser Input
RED/WHT
+
LED LOAD
BLU/WHT
-
RED
+
AC Driver
-
loading