Then three levels of flow are required for the self-learning of three parameters:
Flow
NORMAL FLOW
MINIMUM FLOW
ZERO FLOW
STARTING
...WIZARD
ATTENTION:
if the number
of pumps is 2 or 3
unit), this parameter is also
required:
W = inverter address
- First set the MASTER inverter
with the value W = MS
- Then leave the MASTER
inverter OFF (out of service)
- Then set the SLAVE1 inverter
with the value W = S1
- Then leave the SLAVE1
inverter OFF (out of service)
- Then set the SLAVE2 inverter
with the value W = S2
- Then put into service the
MASTER and SLAVE1 inverters
and the unit will operate
automatically.
Self-learning of the parameter
Correct rotation direction of the motor (models M/T)
Shutdown frequency
Minimum Cosfi (parameter which detects the dry operation of the pump)
SET
L EN
language
N 1
number of
pumps
(pumping
P 4,0
pressure
SS 16
sensor full scale
I 10,5
current
FLOW
motor rotation
(self-learning)
MIN FLOW
off frequency
(self learning)
CLOSED
dry running
(self learning)
OK
confirmed
modify
confirm
modify
confirm
modify
confirm
modify
confirm
modify
confirm
start self-
learning
start self-
learning
start self-
learning
STARTING
31
Only for
inverter
MASTER
Only for
inverter
MASTER
WAIT
SAVE
ROTATION
WAIT
SAVE OFF
FREQUENCY
WAIT
SAVE POWER
FACTOR
OFF