To install, proceed as follows:
unscrew the fixing screws and remove the burner cover.
Disconnect all connections, the 7-pin plug, the probe con-
nector, the high voltage cables and the earth wire from the
control box.
Disconnect the control box from the burner by loosening the
screw A)(Fig. 3) and pulling in the direction of the arrow.
Install the new control box supplied, fixing it to the burner
with the screw A)(Fig. 3) and using a tightening torque of
1 - 1.2 Nm.
Reconnect all connections, the 7-pin plug and the earth
wire.
2.1
Modifying the remote reset connection
If the burner has a remote reset, you must proceed as follows
(Fig. 4):
cut the existing socket-connection.
Make the new connection (RS, see paragraph "Electrical
diagram" on page 7).
Connect a button at a max. distance of 20 metres.
20142714
Installation
4
GB
A
E9275
E9242
Fig. 3