Digital inputs and functions
6.4.3 Analog outputs
The analog output to be set is selected in this display.
As standard, there are three analog outputs. The display shows
each output so that its physical location can be quickly identified.
Example
The AO1 analog output on the IO 351B (designated terminal 18) is
linked to the function "VFD frequency, pump 1".
AO1 (IO351B-41) [18].
Input
Module
AO1
IO 351B
Path:Settings > I/O settings > Analog outputs >
Analog outputs
6.4.4 Digital outputs
The digital output to be set is selected in this display.
As standard, there are nine digital outputs. The display shows each
digital output so that its physical location can be quickly identified.
24
Example
The DO1 digital output on the CU 362 (designated terminal 71) is
linked to "High-level alarm".
DO1 (CU 362) [71] and DO1 (IO351B-41) [77].
Output
DO1
DO1
Path:Settings > I/O settings > Digital outputs >
Terminal
Digital outputs
18
Digital outputs, output value
The output value for the selected digital output is set in this display.
Example
The DO1 digital output on the CU 362 (designated terminal 71) is
linked to "High-level alarm".
Path:Settings > I/O settings > Digital outputs > Function of
digital outputs >
Function of digital outputs
Control unit/module
Terminal
CU 362
IO 351B
71
77