PSU67-3P-1S-2L-24250-F
EN
Quick Start Guide
PSU67-3P-1S-2L-24250-F
Additional documents
The following additional documents are available online at www.turck.com:
■
Data sheet
■
Declaration of conformity
For your safety
Intended use
The power supply unit PSU67-3P-1S-2L-24250-F is a stand-alone power sup-
ply for three-phase mains systems for indoor use.
The devices must only be used as described in these instructions. Any other
use is not in accordance with the intended use. Turck accepts no liability for
any resulting damage.
General safety instructions
■
The device must only be mounted, installed, operated and maintained by
trained and qualified personnel.
■
The device is a "Class of Protection I" equipment according to IEC 61140.
■
The device is designed for pollution degree 3 areas in controlled environ-
ments.
■
Only use the device with additional protective devices in the area of
personal and machine protection.
■
Operate the device exclusively within the technical specifications in order
not to impair the protective function of the device.
■
Do not connect the negative potential of any output externally to PE.
■
Only use the device with a proper PE (Protective Earth) connection.
Product description
Device overview
S. fig. 2: dimensions, s. fig. 3: Block diagram
Functions and operating modes
The power supply provides a stabilized and galvanically separated PELV/ES1
output voltage at the two outputs OUT1 and OUT2. The negative potential of
the outputs is permanently connected to PE in the device.
The outputs are electronically protected against open-circuit, overload and
short-circuit and can supply any type of loads, including unlimited inductive
and capacitive loads.
The device is equipped with an over-temperature protection. In case of a
over temperature, the device shuts down and starts automatically again
after cooling off. The outputs return to the state they had before being
switched off.
In case of an internal defect, a redundant circuit limits the maximum output
voltage to 32.5 V. The outputs are shut down and restart automatically if the
defect is eliminated.
Installation
General installation instructions
The unit is suitable for use at altitudes up to 5000 m (16400 ft). Above 2000
m (6560 ft), the output current and overvoltage category must be reduced.
When using the device in TN, TT and IT networks the following applies:
■
TN, TT mains systems with earthed neutral and IT star mains systems with
insulation monitoring: Use in zones of overvoltage category III up to an
altitude of 2000 m (6560 ft), use in zones of overvoltage category II up to
an altitude of 5000 m (16400 ft)
■
TN, TT, IT delta mains systems or IT star mains systems without insulation
monitoring: Use in zones of overvoltage category II up to 2000 m (6560 ft)
The device uses convection cooling. An external fan is not necessary.
Special mounting instructions
CAUTION
Sharp edges on the back of the device
Risk of injury
Mount the devices on a sufficiently large, even surface so that all sharp
➤
edges are covered.
Mount the device vertically with the connection level facing downwards
➤
on a flat surface using two screws each (M4 or UNC 8-32) at the upper and
lower mounting holes.
Other mounting orientations: reduce the output current.
➤
Do not obstruct airflow. Do not cover ventilation fins.
➤
Observe the minimum installation clearances: 50 mm on top and bottom,
➤
10 mm on the front and 10 mm left and right side.
Connecting
Connect the device according to "Wiring diagrams".
➤
Mating connectors
■
Input voltage (XD1): M12 female connector, S-coded, 4-pin
■
Relay OK signal (X0): standard M12 female connector, 5-pin, A-coded
■
Output voltage (XD2, XD3): M12 male connector, L-coded, 5-pin
Appropriate accessories can be found at www.turck.com. The accessories
are not part of the scope of delivery.
Do not apply return voltages from the load to the output higher than 35 V.
➤
Do not connect outputs or devices in parallel.
➤
The device is designed, tested and approved for branch circuits up to 20 A
(UL) and 32 A (IEC) without additional protection device.
①
PSU67-3P-1S-2L-24250-F
IP67 Power Supply
Quick Start Guide
Doc. no. 100032473
Additional
information see
turck.com
②
38
20
182 [7.17]
[1.50]
[0.79]
168.2 [6.62]
163.7 [6.45]
107
[4.21]
4.5
[0.18]
M12 × 1
M12 × 1
M12 × 1
M12 × 1
mm [Inch]
③
Temperature
Output
Shutdown
OVP
Output
Power
Manager
DC OK
Power
Converter
Input
L1
+
Switchable
Fuse
1
L2
Output
Filter
2
-
L3
PFC
3
Recti er
Inrush Current
PE
4
Limiter
XD1
④
Trip Delay/s
[A]
2 3 4 5 6 8 10 12
100
10
1
10
-1
10
-2
10
-4
10
-5
0
5
10
15
20
25
30
35
40
© Hans Turck GmbH & Co. KG | 100032473 2023-06
59 [2.32]
56.3 [2.22]
183
195.4
[7.21]
[7.69]
LED bar
Status
Set
1
ROK
4
X0
Output
+
1
4
Out 1
2
3
-
FE
XD2
+
1
4
Out 2
2
3
-
FE
XD3
45
50
I
/A
(typ.)
Out