INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR MODEL
TC808E1028M01 PLUG-IN INTELLIGENT RATE OF RISE TEMPERATURE
Before installing the sensor, please thoroughly read System Sensor's wiring and installation manual, I56-407-XX, Guide for Proper Use of System
Smoke Detectors. This manual includes detailed information on sensor spacing, placement, zoning, and special applications. Copies of this
manual are available at no charge from Honeywell.
GENERAL DESCRIPTION
Model TC808E1028M01 intelligent rate of rise temperature (Class A1R) sensors use a state-of-the-art single thermistor sensing circuit to
provide early warning of developing fires. These sensors are designed for open area protection and must only be connected to control
panels that use a compatible proprietary analogue addressable communication protocol for monitoring and control.
Two LEDs on each sensor light to provide a local 360° visible sensor indication. The LEDs can be latched on by code command from the control
panel for an alarm indication. The LEDs can also be unlatched to the normal condition by code command. Remote LED indicator capability is
available as an optional accessory wired to the standard base terminals.
SPECIFICATIONS
Operating Voltage Range:
15 to 32 VDC
Max. Standby Current:
200µA @ 24 VDC (no communication)
Max. Avg. Standby Current:
300µA (one communication every 5 sec. with LED blink enabled)
Max. Alarm Current (LED on):
7 mA @ 24 VDC
Operating Humidity Range:
10% to 93% Relative Humidity, non condensing
Temperature Range:
-30°C to 80°C
Nominal Activation temperature:
58°C or 10°C / min
Height:
51 mm installed in B501 Base
Diameter:
102 mm installed in B501 Base
Weight:
78 g
This detector has been independently tested and certified to prEN54 Part 5 Class A1R.
WIRING GUIDE
Refer to the installation instructions supplied with the plug-in sensor bases for wiring details. All bases are provided with terminals for power,
shield, and an optional Remote Indicator.
NOTE: All wiring must conform to applicable local national codes and regulations.
NOTE: Verify that all sensor bases are installed and that polarity of the wiring is correct at each base.
Disconnect loop power before installing sensors.
SENSOR INSTALLATION
1.
Set the sensor address (see Figure 1) by using a flat blade screwdriver to turn the two rotary switches, selecting the desired number
between 01 and 99. Record the address on the label attached to the base.
2.
Insert the sensor into the base and rotate it clockwise with gentle pressure until it drops into place.
3.
Continue to rotate the sensor until it locks into the base.
4.
After all sensors have been installed, apply power to the system.
5.
Test the sensor as described under TESTING.
6.
Reset the sensor by communication command from the panel.
Tamper-Resistance
Model TC808E1028M01 includes a feature that, when activated, prevents removal of the sensor without the use of a tool. Refer to the installation
6 7
8
7
8
9
6
9
5
5
4
4
3
3
2
2
1
1
0
0
TENS
ONES
instructions for the sensor base for details of how to use this feature.
MAINTENANCE
Before cleaning, notify the proper authorities that the system is undergoing maintenance and will be temporarily out of service. Disable the
system to prevent unwanted alarms.
It is recommended that the sensor be removed from its mounting base for easier cleaning and that sensors be cleaned at least once a year
H600-04-00
SENSORS
WARNING
Figure 1. Rotary Decade Address Switches.
TEST
MAGNET
LED
LED
TEST MAGNET
Use a vacuum cleaner to remove dust from the sensing chamber.
TESTING
Detectors must be tested after installation and following periodic maintenance.
However, before testing, notify the proper authorities that the system is undergoing
maintenance and the system will be temporarily out of service. Disable the zone or
system undergoing maintenance to prevent unwanted alarms.
In addition, check to ensure that the LEDs blink (if this feature is operational under
software command). If they do not, power has been lost to the sensor (check the
wiring), or it is defective (return it for repair).
Test the sensors as follows:
Test Magnet (Model M02-24 - optional)
1.
Test the sensor by positioning the optional test magnet against the sensor
body approximately 2 cm from LED in a clockwise direction, as shown in
Figure 2.
2.
Both LEDs should latch on within 30 seconds, indicating an alarm and
activating the panel.
Control Panel
1.
Test the sensitivity from the control panel.
Direct Heat Method (Hair dryer of 1000-1500 watts).
1.
Direct the heat toward the sensor from its side. Hold the heat source about
15 cm away to prevent damage to the cover during testing.
2.
The LEDs on the sensor should light when the temperature at the detector
reaches 58°C. If the LEDs fail to light, check the power to the sensor and the
wiring in the sensor base.
3.
Reset the sensor at the system control panel.
After completion of all tests notify the proper authorities that the system is
operational.
Sensors that fail these tests should be cleaned as described under
MAINTENANCE and retested. If the sensors still fail these tests they should be
returned for repair.
Heat sensors are designed to protect property, not life. They do not provide early warning of fire and cannot detect smoke, gas, combustion
particles or flame. The TC808E1028M01 alarms when temperature at the heat sensor reaches 58°C. Given the rapid growth of certain types of
fire, heat sensors cannot be expected to provide adequate warning of fires resulting from smoking in bed, inadequate fire protection practices,
violent explosions, escaping gas, improper storage of flammable liquids like cleaning solvents, other safety hazards or arson.
Heat sensors do not always detect fires because the fire may be a slow smouldering, low-heat type (producing smoke) or because
they may not be near where the fire occurs or because the heat of the fire may bypass them. Heat sensors will not detect smoke, gas,
flames or combustion particles.
Heat sensors are components in professionally installed fire alarm systems. They will not function if they have been improperly wired into
the fire alarm system or if power to them is cut for any reason.
Heat sensors cannot last forever. They should be tested and maintained following the instructions in this manual. To be safe, they should be
replaced after they have been installed for 15 years.
1
Honeywell Fire and Security, Europe
Figure 2. Test Magnet Positioning.
Figure 3. Sensor
WARNING
LIMITATIONS OF HEAT SENSORS
© System Sensor 2001
I56-1312-001
loading

Resumen de contenidos para Honeywell TC808E1028M01

  • Página 1 Reset the sensor by communication command from the panel. returned for repair. Tamper-Resistance Model TC808E1028M01 includes a feature that, when activated, prevents removal of the sensor without the use of a tool. Refer to the installation WARNING LIMITATIONS OF HEAT SENSORS Heat sensors are designed to protect property, not life.
  • Página 2 DESCRIZIONE GENERALE I rivelatori di calore velocimetrici indirizzabili modello TC808E1028M01 (Classe A1R) utilizzano un circuito elettronico di rilevazione a singolo termistore per la segnalazione di incendi. Tali rivelatori sono progettati per la protezione di aree aperte e devono venire collegati solo a pannelli di controllo funzionanti con protocollo di comunicazione proprietario compatibile di tipo analogico ad indirizzi per il monitoraggio e il controllo.
  • Página 3 ADVERTENCIA El modelo TC808E1028M01 dispone de una opción que, si se utiliza, impide extraer el sensor si no es mediante el uso de herramientas. Consulte las instrucciones de instalación de la base del sensor si desea más detalles sobre el uso de esta utilidad.
  • Página 4 Melder, die den Test nicht bestanden haben, müssen wie unter WARTUNG beschrieben gereinigt und erneut getestet werden. Wenn die Melder Das Modell TC808E1028M01 enthält eine Funktion die - wenn sie aktiviert ist - verhindert, daß der Melder ohne den Gebrauch von Werkzeugen dann bei diesen Tests immer noch nicht funktionieren, müssen sie zur Reparatur eingesandt werden.