COMMUNICATION

NB:
• The integration time must not exceed
3 silences (the time taken to transmit
a character) for the message to be
processed.
• By selecting slave address 0, the
same message is transmitted to all
the Countis devices present on the
network (only for functions 6 and 16).
NB:
A maximum of 60 words can be read
in one frame.
Address
Decimal
Hexadecimal
768
300
770
302
772
304
774
306
776
308
778
30A
780
30C
782
30E
784
310
786
312
788
314
24
The Countis Ci system communicates via a JBUS/MODBUS
ving a master/slave dialogue. Two dialogues are possible:
• the master communicates with a slave (Countis Ci) and waits for its response,
• the master communicates with all the slaves (Countis Ci) without waiting for
their response.
The communication mode is the RTU mode (Remote Terminal Unit) with
hexadecimal characters consisting of 8 bits.
COMMUNICATION FORMAT
This is a standard format consisting of:
Slave address
The following functions are essential in order to make full use of information:
3
to read n words (128 maximum )
6
to write a word
8
to diagnose master/slave exchanges from meters 1, 3, 4, 5 and 6
16
to write n words (128 maximum)
DISPLAY (FUNCTION 3)
METERS
METERS DISPLAY
N° of words (1)
Totalizing meters
2
2
2
2
2
2
2
Pulse meters for power demand storing
2
Value between 2 signals for input 1
2
Value between 2 signals for input 2
2
Value between 2 signals for input 3
2
Value between 2 signals for input 4
Function code
Address
Description
Meter 1
Meter 2
Meter 3
Meter 4
Meter 5
Meter 6
Meter 7
Zone size (1): 22 words in decimal or 16 in hexadecimal.
®
protocol invol-
Data
CRC16
Unity
0.01 kWh
in energy metering
and no value in pulses
Pulses
SOCOMEC - Ref. : 875 092A