S&P CADS-HE Instrucciones De Uso página 10

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

MAINTENANCE
Filters
 Unlock the 4 fasteners on the cover (take care to keep the cover with one hand during this operation to avoid falling by
gravity (risk of damage to the cover and risk of injury).
 Remove the cover.
 The filters should be inspected regularly and changed at least once a year.
Exchanger
 Unlock the 4 fasteners on the cover (take care to keep the cover with one hand during this operation to avoid falling by
gravity ( risk of damage to the cover and risk of injury).
 Remove the cover.
 Remove the metal strip which secure the heat exchanger.
CAUTION: keep the heat exchanger with one hand during this operation to avoid falling by gravity (risk of damage to the
heat exchanger and risk of injury).
 Take care not to damage the fins of the heat exchanger.
 The heat exchanger should be inspected regularly and cleaned at least once every 2 years.
 Clean the heat exchanger with compressed air or vacuum cleaner. Use non agressive detergents.
CAD HR S WITH BY-PASS VERSION
Utilisation
The use of by-pass allows take cold night air in summer which can then be used it for during the day. ( free cooling)
The control can be either local (eg switch placed in the room of a commercial building or housing in an apartment
building) or centrally (eg apartment buildings).
Characteristics
Electrical supply 230 V, I<100 mA
Intensity < 100 mA
Note : The servomotor has integrated magnet for gear disengagement. Manual override with magnet possible (the gear is
disengaged as long as the magnet adheres to the symbol).
WIRING
Before any intervention, PUT YOUR EQUIPMENT WITH LOW PRESSURE.
 Blue wire No 1 connected to the neutral.
 Brown wire No 2 connected to the phase.
 White wire No 3 zero potential (switch open), the by-pass is closed: the
airflow pass through the heat exchanger.
 White wire No 3 connected to the phase (switch closed), the by-pass is
open: the airflow doesn't pass through the heat exchanger.
Dealing with products at the end of their life:
To contribute to environmental protection and optimisation of natural resources, this product should be recycled at the end of its useful life. It should not be
disposed of in a landfill or treated as household waste but must be deposited at a collection point for recycling electrical and electronic equipment. For further
information about recycling of this product, please contact: the Agency for Environment and Energy Control in your area, your consular chamber (CCI or Chamber of
trades and the crafts), your municipality, your household waste disposal unit.
Note: to the extent that the equipment sold is professional electrical and electronic equipment covered by Decree No. 2005-829 of 20 July 2005 implementing Directive 2002/96/EC of 27
January 2003, the owner of this equipment will, unless otherwise agreed, fund and organise the waste disposal of this equipment under the conditions defined in Articles 21 and 22 of the
Decree.
Couple 2 N.m.
Consumption 1.5W
10
N L
1 2 3
CM230
Tabla de contenido
loading

Tabla de contenido