2.1 Position of the stove / distance requirements
Please make sure that the fireplace insert is installed in a suitable and physically possible position. You need
to be sure that the position complies with local regulations. Distance requirements will only apply if the
fireplace insert is to be placed close to flammable materials. See below:
Distance to flam-
mable material (cm)
Aduro 5.1
It is possible to reduce the distance to flammable material by insulating with at least 5.0 cm insulation with
identical properties to Aduro Superisol, Isolrath 1000 or similar material around the Aduro 5.1. Please make
very sure that there is still at least a 2.5 cm space around the Aduro 5.1. This means that the distance to
flammable material can be reduced to 7.5 cm (2.5 cm space around the insert + 5 cm insulation):
Behind the stove
25
Distance to
To the sides
30
2,5 cm space
Minimum height
furniture
above floor level
110
5,0 cm insulation
Flammable material
26
32