Using the Digital Display
OUTLET INDICATOR LED DEFINITIONS:
LED Configuration
Standard
1
Alternate
1 This is the default configuration.

Display Options

LED Test
Hold the Mode button for 3 seconds to test the display. For 5 seconds, all LEDs and display
segments will light green, while all Load Indicator LEDs will light yellow. Please visit www.tripplite.
com/support for issues with display segment or Indicator LED functionality.
Viewing the IP Address
i P
i
18-11-311-9332D2.indb 13
LED Color
Outlet Status
Off
Off
Green
On
Yellow
On
Red
Off
Red Flashing
Off
Off
Off
Red
On
Red Flashing
On
Green
Off
Green Flashing
Off
8 8 8
88
At any point, pressing both of the arrow buttons simultaneously for 1/2
second displays the unit's IP address in the 2-digit display.
To Rotating the Display
Description
Outlet power is absent
Circuit breaker is on – Outlet power is present
Bank has exceed 80% of its current rating – Bank
power is present
Bank is below the Low Voltage threshold – Bank
power is absent
Circuit breaker has tripped – Bank power is absent
Outlet power is absent
Circuit breaker is on – Outlet power is present
Outlet's bank has exceeded 80% of the outlet current
rating – Outlet power is present
Bank is below the low voltage threshold – Bank power
is absent
Circuit breaker has tripped – Bank power is absent
13
1/23/2019 6:19:43 PM