Install the Flood Sensor and Activation Module
The activation module receives a signal from the flood sensor when a discharge is detected.
If the discharge meets the conditions of a qualifying event, the normally open contact is closed to
provide a signal to the BMS input terminal.
The flood sensor and assembly shown in the installation sequence are representative only. Each flood
sensor is designed specifically for the assembly to which it is attached.
Custom Flood Sensor Settings
The default settings on the activation module for detecting discharge are suitable for
the assembly series. However, the DIP switches can customized for a different wet
threshold and time delay. Scan the QR code for more information.
1. Remove the dust cover from the sensor.
3. Check that the module is fully seated to seal the O-ring and
to make electrical contact.
2. Press the activation module onto the sensor.
NOTICE
Retain the dust cover to protect the flood sensor when the
activation module needs to be removed or replaced.