4 Door accesscontrol unit withweb access
QUICK USERGUIDE
DESCRIPTION
WS4-4D-Eis a 4 door control unit designed to operate with readers with RS485 output.
There is no need to install any software. There is no need to have a dedicated PC
either. Everything is available online and the operators just need to register with
controller's serial number to start using the software application.
SPECIFICATIONS
•:Capacity:
2500 Users
•:Events:
50000 max.
•:Doors:
4 (max. 20 doors in same network)
•:Readers:
4
•:Door contact inputs:
4
•:Pushbutton inputs:
4
•:Auxiliary Inputs:
2 (emergency, vehicle detection)
•:Auxiliary Outputs:
2 (alarm, storing alarm status, presence)
•:Power supply:
120 to 240 V AC, 100 VA-1.52Awith fuse (1A)
•:Supply for the readers:
225 mA each max.
•:Supply for the locks:
600 mA each max.
•:Relaycharacteristics:
2A/48 VAC/DC#
•:Processor:
ARM A5 - 528 Mhz
•:Memory:
64 MB Ram DDR2 133 Mhz
•:TCP/IPconnection:
10/100/1000 Base-T– HTTPor HTTPS
•:Dimensions (mm):
116x 195 x 33 mm
•:Operating temperature:
0 °C to +50 °C
•:Humidity:
0%to 85%(non-condensing)
•:Tamper:
Yes
•:Wiegand readers connection:
Yes, via Wiegand to RS485 converter - WS4-CNV
•:Elevator feature:
Yes, 2 elevators per installation, each - 24 floors
•:Interlock, Anti pass back, people counter, presence, system logs, reports in CSV
FIRSTCONNECTION AND CONFIGURATION
The WS4-4D-E does not have default IP address. By default is set to DHCP. There are 2
methods to connect to and configure WS4-4D-E- LAN and Standalone method.
METHOD 1
(For use in a home or business LAN network)
In this configuration, the network's DHCPserver will assign an IPaddress to your WS4-4D
1. Put the DIP switch 1in position OFF.
2. Connect a cable from your network to the ethernet connector of WS4-4D-E.
3. Open a web browser and enter http://ws4 followed dash and the serial number of
the WS4-4D-Econtroller
If you can not connect, it is because your network does not recognize the name of the
EN
WS4-4D-Econtroller. In this case,go to our web site http://www.xprgroup.com/products/ws4/
and download the tool called "Device Finder".
The "Device Finder" will enable you to find out the IPaddress of the WS4-4D-Econtroller.
Run the "Device Finder" and you will get a list of all the WS4 controllers connected in
your network, including their IP addresses,just like the picture below.
Open a browser and type the IPof the WS4-4D-Econtroller and you will be prompted to the
login page.
User Name: admin
Password:WS4 followed by Dash and the SerialNumber (ex. WS4-110034) just like the
image below, all in capital letters without space.
METHOD 2
(For standalone use - without LAN network)
In this configuration, the WS4-4D-Ewill assign an IPaddress to your PC. The PC must be set to obtain IP
address automatically.
1. Put the DIP switch 1in position ON.
2. Connect a cable from your PCdirectly to the ethernet connector of WS4-4D-E.
3. Open a web browser and enter the following IP - 192.168.50.100,thenput the login
credentials like explained above
FACTORY RESET
DIPSwitch 4 allows a complete re-initialization of the system. To
do this, switch this dip switch 3 timesOFF- ON - OFF within 10
seconds.
CHANGE PASSWORD
DIPSwitch 4 allows to log into the system as an administrator if
login or password is forgotten. Toggle this dip switch ON for
about 15 seconds, then back to OFF. The system will then allow,
for 5 minutes, to connect (from the local network only) with the
default login and password.
SOFTWARE SETTINGS
ADDING READERS
Go to "Doors", select the reader(fig.2)and then select the type of the reader in the
field "Card". (fig.3). While off line, red LEDblinks fast and buzzer beeps continuously.
Once communication is established, the red LEDand the buzzer stop. Green LED
starts to blink continuously. If you want to stop the green LED,go to Settings/System
Options and select for the backlight ON or OFF(not default) fig.4
www.xprgroup.com
fig.1
fig.3
fig.5
To add 2 readerson 1Door, select the reader (fig.2) and there, for "Type of Access"
select "Access with 2 readers" (fig 5). Fill the form for both readers and they will
merge in one door (fig. 6)
ADDING USERS
Go to Users (fig.1),select "New"(fig.2) and then fill the form (Name, category, card
number...)(fig.3).
fig.1
fig.2
ADDING SLAVE CONTROLLERS
WS4 system can manage up to 10 WS4 boards in the same installation (with up to 20
doors, whether single or double). One WS4-4D-Emust be master, the others must be
slaves. The master/slave selection is made with Dip-switch 2: OFF - Master (factory
setting), ON - Slave.
Go to "Doors" and click on the link "Add slave"(fig.1).Enterthe serial number of the
WS4-4D-Eto be added and click Search. If it finds it, the system directly adds this slave
into the installation and you can configure its doors (fig.2).
In case of error, a message is displayed in red.
Switch
fig.1
Master
Slave9
Slave1
DIPswitch 2
DIPswitch 2
DIPswitch 2
OFF
ON
ON
Master/
Slave
fig.2
fig.2
fig.4
fig.6
fig.3
3
EN