4. INSTALLATION
4.6 "BACK-UP" short-circuit protection:
The VCL Slim is equipped with an isolator switch (thermal and electrical disconnect
system) capable of interrupting short-circuit currents of up to 5 kA. If the short-circuit
current at the installation point exceeds 5 kA, a backup short-circuit protection as
short-circuit protection. CLAMPER recommends a fuse of CLAMPER recommends a
Diazed, 63 A timed fuse, or NH, type gL/gG with a maximum of 100 A.
F1
F2
Attention
If fuse F1 has a lower current rating than the backup fuse, it is not necessary
to use fuse F2.
CLAMPER Indústria e Comércio S.A.
E/I
www.clamper.com.br
|
F1
F2
16103133
+55 31 3689 9500
E/I
Page 36 of 44