Place the extra seal cover at the top of the recess in the casing.
Putting the appliance in place:
*
Ensure the floor has sufficient weight bearing capacity for the appliance.
*
Make sure all the combustion air supply openings are clear.
*
If the appliance is placed in a situation with the discharge pipe fitted in front of a non-combustible
wall, the distance between the appliance and the non-combustible wall must be at least 100 mm.
*
If placed against a flammable wall, the distance from the back of the appliance to the wall must be
at least 200 mm.
*
Sufficient shielding must be used with a combustible wall if a single or double-walled discharge pipe
is used.
*
For a flammable floor, use a fire-resistant floor plate that protrudes at least 300 mm in front of the
appliance.
*
All other distances to flammable materials around the appliance must be at least 800 mm.
*
Make sure the right type of fire extinguishers are on hand in the event of an emergency.
*
Put the appliance in place in the correct position and use the adjustable feet to level the appliance.
*
Connect the discharge duct gas-tight.
*
Connect the direct external air supply to the external air connection under the appliance
using non-combustible discharge material with a diameter of 80 mm.
4.
FLUE GAS DUCT
The following requirements are applicable to the flue gas duct:
*
the flue gas duct must be inspected in advance by a specialist.
*
the flue gas duct must be suitable for connecting a wood-fired appliance.
*
the appliance must be connected to a single, undivided flue gas duct.
*
the flue gas duct must be clean.
*
the flue gas duct must be gas-tight.
*
the offset in the flue gas duct must no exceed 1.5 metres, with a
minimum angle of 45 degrees from the horizontal plane.
*
for a rear connection to the appliance, the horizontal part of the flue gas
duct must not exceed 500 mm. It must then go vertically upwards.
*
when connecting the rear connection of the appliance to a vertical flue
gas duct, a T-piece with soot bag must be used.
*
the diameter of the flue gas duct must be at least equal to the diameter of the
flue gas discharge of the appliance.
*
the draft of the flue gas duct must be at least 12 Pascal.
*
a flue gas damper must be fitted in the event of the draft being too strong.
*
stove pipes must be installed with discharge towards the appliance.
*
the flue gas duct must be self-supporting and must not rest on the appliance.
Installation and operating instructions
15
Trimline Woody Loft