1. Open the ball valve by turning the rinse
knob. Rinse knob must be vertical.
2. Close the ball valve after approximately
15 seconds.
NOTE:
A longer rinse period may be
necessary if the filter is very
dirty (Replace filter mesh see
Maintenance)
15s
2
Fig. 3. Rinsing the filter.
Pressure Reducing Valve
Replacing the Cartridge (Fig. 4)
The working parts of the FK06, including
diaphragm, valve seat, strainer, and disk are
all contained in a replaceable cartridge. To
replace the cartridge:
1. Close shutoff valve on inlet.
2. Release pressure on outlet side (e.g.
through water tap).
1
M36610A
BRAUKMANN FK06 DIALSET®
3. Close shutoff valve on outlet.
4. Loosen slotted screw (do not remove
the screw).
CAUTION
To prevent injury and/or equipment
damage, loosen locknut and turn
adjusting screw counter-clockwise
to remove spring tension.
5. Slacken tension in compression spring
by turning counter clockwise until it
does not move anymore.
6. Unscrew Bonnet.
7. Remove slip ring.
8. Remove cartridge using a pliers as a
lever.
9. Reassemble bonnet in reverse order.
Recalibrate
If the dial knob assembly has been
disassembled recalibration is necessary.
1. Close shutoff valve on inlet.
2. Release pressure on outlet side (e.g.
through water tap).
3. Close shutoff valve on outlet.
4. Remove dust cap.
5. Loosen slotted screw (do not remove
screw).
6. Fit pressure gauge.
7. Slowly open shutoff valve on inlet.
8. Set desired outlet pressure (e.g. 60 psi).
9. Align scale (e.g. 60 psi) in middle of
viewing window.
10. Re-tighten slotted screw.
11. Slowly open shutoff valve on outlet.