A105N APPELLO
12, 24vdc
-
+
S2
Stage 2
115, 230vac
S2
C
L~
N~
Stage 2
Stage 1
Frequency Description
Tone 1
800/1000Hz @ 0.25 sec Alternating
Tone 2
500/1200Hz @ 0.3Hz 0.5 sec Slow Whoop
Tone 3
1200/500Hz @ 1Hz - DIN / PFEER P.T.A.P.
Tone 4
544Hz (100mS)/440Hz (400mS) - NF S 32-001
Tone 5
1000Hz Continuous - PFEER Toxic Gas
Tone 6
Bell
Tone 7
1KHz 1s on, 1s off Intermittent - PFEER Gen. Alarm
Tone 8
420Hz @ 0.625 sec Australian Alert
Tone 9
500-1200Hz 3.75sec /0.25sec. Australian Evac.
Tone 10
No tone - 0.5 second gap
Tone 1
Tone 2
Tone 3
Tone 4
Tone 5
A105N
A105N
APPELLO
APPELLO
AC
DC
130,00
APPELLO
Ø7,00
144,00
144,00
AC terminal
130,00
enclosure
Ø7,00
Cycles
4 cycles
2 cycles
4 cycles
4 cycles
2 cycles
2 cycles
3 cycles
4 cycles
2 cycles
Tone 6
Tone 7
Tone 8
Tone 9
Tone 10
- 10 Tone Voice Annunciation Sounder
DESCRIPTION
The E2S Appello Speech and Tone unit has the facility to record, store and playback user defined messages. The user has the
option of recording a single message up to 16 seconds or two messages up to 8 seconds each. The recorded message(s) can
then be played back preceeded by the choice of one of nine tone functions, which are selected 'On Board' by the user.
Alternatively the message can be played back without the presence of the tone.
IMPORTANT:
AC units supply termination PCB is contained in the external enclosure.
CONNECT AC TO THIS PCB ONLY.
THE COVER MUST BE REPLACED BEFORE OPERATION.
DAMAGE WILL OCCUR TO THE UNIT IF THE SUPPLIED VOLTAGE IS NOT WITHIN THE LIMITS SPECIFIED.
NOTE: DUE TO THE HIGH SENSITIVITY OF THE 'ON BOARD' MICROPHONE ENSURE ALL BACKGROUND NOISE IS KEPT
TO A MINIMUM DURING RECORDING.
A105N
RECORDING A SINGLE MESSAGE UP TO 16 SECONDS.
DC
•
Select 'Record Mode' - link LK1 set to 'REC'.
•
Select Message 2 - link LK4 set to 'M2'.
•
Apply power.
•
126,00
To record press the 'Push Switch' SW1 and hold while speaking into the microphone. Ensure that the message does
not exceed 16 seconds otherwise the part of the message after 16 seconds will not be recorded.
•
IF THE LED INDICATOR IS NOT ILLUMINATED AT THE END OF RECORDING: THE MESSAGE HAS EXCEEDED
16 SECONDS AND WILL NEED TO BE RECORDED AGAIN IN ORDER TO 'PLAY BACK'.
RECORDING TWO MESSAGES OF UP TO 8 SECONDS.
•
Select 'Record Mode' - link LK1 set to 'REC'.
•
Select Message 1 - link LK4 set to 'M1'.
•
Apply power.
•
To record press the 'Push Switch' SW1 and hold while speaking into the microphone. Ensure that the message does
A105N
not exceed 8 seconds otherwise the part of the message after 8 seconds will not be recorded.
•
APPELLO
IF THE LED INDICATOR IS NOT ILLUMINATED AT THE END OF RECORDING: THE MESSAGE HAS EXCEEDED 8
AC
SECONDS AND WILL NEED TO BE RECORDED AGAIN IN ORDER TO 'PLAY BACK'.
•
Select Message 2 - link LK4 set to 'M2' and repeat as per message 1.
126,00
NOTE: If Message 2 exceeds 8 seconds it will record OVER Message 1. Please note that the LED will not turn off to
show that the message has exceeded 8 seconds.
PLAYBACK OF RECORDED MESSAGES.
•
Remove connectors from link LK1 and link LK4.
•
Select the desired tone using link LK5 - connector settings are shown in the tone table. The Appello is factory set
to the tone length as shown in the tone table. To double the length of the tone connect the two far right pins of LK5. If
the unit is set for no tone between messages (Tone 10) the gap will increase from 0.5 seconds to 2 seconds if the
tone length link is fitted.
•
Supply power and Message 1 will playback, the selected tone will sound and the message will repeat.
•
If two messages have been recorded, to 'Play Back' Message 2, connect terminal block position S2 to '-'. Message 2
will then 'Play Back', the selected tone will sound and then Message 2 shall repeat. On AC units connect terminal
block positions S2 and C on the AC input PCB.
•
Output volume can be adjusted with potentiometer P1.
Voltage :
Voltage range :
Current mA :
12vdc
24vdc
115vac
230vac
50/60Hz
50/60Hz
9-15vdc
18-30vdc
+/-10%
+/-10%
150mA
180mA
40mA
20mA