Varios Tipos de Energía
W[i]
∑
Wh [ 0 ][ i ] =
3600
Tint
VA[i]
∑
VAh [ 0 ][ i ] =
3600
Tint
∑
VARhL [ 0 ][ i ] =
Tint
∑
VARhC [ 0 ][ i ] =
Tint
Energía activa total consumida:
Wh[0][3] = Wh[0][0] + Wh[0][1] + Wh[0][2]
Energía aparente total consumida:
VAh[0][3] = VAh[0][0] + VAh[0][1] + VAh[0][2]
Energía reactiva capacitiva total consumida:
VARhC[0][3] = VARhC[0][0] + VARhC[0][1] + VARhC[0][2]
Energía reactiva inductiva total consumida:
VARhL[0][3] = VARhL[0][0] + VARhL[0][1] + VARhL[0][2]
W[i]
∑
Wh [ 1 ][ i ] =
3600
Tint
VA[i]
∑
VAh [ 1 ][ i ] =
3600
Tint
∑
VARhL [ 1 ][ i ] =
Tint
∑
VARhC [ 1 ][ i ] =
Tint
Energía activa total consumida:
Wh[1][3] = Wh[1][0] + Wh[1][1] + Wh[1][2]
Energía aparente total consumida:
VAh[1][3] = VAh[1][0] + VAh[1][1] + VAh[1][2]
Energía reactiva capacitiva total consumida:
VARhC[1][3] = VARhC[1][0] + VARhC[1][1] + VARhC[1][2]
Energía reactiva inductiva total consumida:
VARhL[1][3] = VARhL[1][0] + VARhL[1][1] + VARhL[1][2]
PowerPad
Modelo 3945-B
®
Energía activa consumida en fase i+1
Energía aparente consumida en fase i+1
VAR[i]
for VAR[i] ≥0
3600
–VAR[i]
for VAR[i] ≤0
3600
Energía activa consumida en fase i+1
Energía activa consumida en fase i+1
–VAR[i]
for VAR[i] ≤0
3600
VAR[i]
for VAR[i] ≥0
3600
Energía reactiva inductiva consumida en fase i+1
Energía reactiva capacitiva consumida en fase i+1
Energía reactiva inductiva consumida en fase i+1
Energía reactiva capacitiva consumida en fase i+1
93