NOTE: When programming Toggle Options, a toggle is ON
when the number is displayed and a toggle is OFF when
the number is not displayed. (e.g., [1---5---], Toggle
Options 1 and 5 are ON, all others are OFF).
2. Program Panel Section [167] Interface Communications Wait
for ACK value as 060 (seconds).
3. When the communicator is installed with the PC9155 panel,
2 telephone number are available to backup one another. You
can set up these telephone numbers to perform in one of two
ways: Backup dialling or Alternate dialling.
a. Backup dialling: each of the 2 telephone numbers will
make 5 dialling attempts in turn, before a Failure To Com-
municate (FTC) trouble is generated to the keypad.
b. Alternate dialling: each telephone number makes 1 dial-
ling attempt before moving on to the next number, cycling
through each of the numbers for a total of 5 times each. If
both numbers fail the 5 attempts, an FTC trouble is dis-
played on the keypad.
4. Panel Sections [301], [302], [303], and [305] can be config-
ured as Primary communication paths.
a. Panel Sections [302], [303], and [305] may also be con-
figured for backup or redundant communications by using
Panel Sections [383] or [351] - [376]. Refer to the
PC9155 panel Installation Manual for more information.
b. If a valid telephone number is programmed, communica-
tions will use Public Switched Telephone Network (PSTN).
Entering a 4 digit hexadecimal value (followed by a single
character F) for a telephone number will change the call
routing as determined by the value programmed:
DCAAF:Internal Routing (Both Receivers). Signals will be
routed depending on the module programming.
DCBBF:Ethernet Receiver 1 (Primary).
DCCCF:Ethernet Receiver 2 (Backup).
5. Panel Section [350]: If any of the phone numbers have been
programmed as DCAA, DCBB, or DCCC, panel Section [350]
must be set to [04] for SIA format or [03] for Contact ID format.
6. Panel Section [382]: Toggle Option [5], Ethernet Module Enabled, must be set to ON. If this option is OFF, the yellow status LED will indi-
cate 'Panel Supervision Trouble' (2 flashes) and the unit can not be programmed via PC-LINK cable.
7. Panel Section [401]: Toggle Option [1] must be set to ON in order to perform panel DLS sessions using Ethernet.
Power Save Feature
The TL265 has a power save mode fea-
ture. If there is an AC power loss on the
PC9155 Control Panel, the system will
enter power save mode to extend battery
duration. During power save mode, the
Ethernet functionality is turned OFF and
will only turn ON when an event needs to
be transmitted or when a firmware
update is required.
• When in power save mode, incoming
DLS connections will not be possible.
• The Link activity LED on the NID will also
be OFF.
Communicator Troubles displayed on a
PC9155 Panel
The following troubles will appear on the
keypad LCD when encountered by a
Communicator on the PC9155 panel.
Please refer to PC9155 Installation Man-
ual for more information.
.
TROUBLE CONDITION
Alternate Communicator Trouble
PC9155
UA558
NOTE: For wiring details for the PC9155,
refer to Installation Manual.
T-1 R-1 TIP RING IO2 IO1 -AUX AUX+ AC AC
INPUT RATINGS (from PC-Link)
11.1V - 12.6 V
DC
100mA Standby
400mA Alarm
DESCRIPTION
Ethernet trouble, central station receiver trouble, supervision
config for /IP module (if installed). Press < > to scroll.
5
Figure 4 PC 9155 Control Panel
Yellow
PC9155
Red
Red
Wire
Green
Green
Gently slide connector away from terminal
BATTERY
Do not disconnect the battery cable from the alarm controller board;
the battery shall be disconnected from the + (PLUS) TERMINAL.
Figure 5 PC 9155 (TL265) Wiring Diagram
RED
Status
LEDs
Red
Wire
Network Connection
Use only CAT5 cable
Supervised.
Table 4: Communicator Troubles on a PC9155
Check LAN connections.
Call for service.
TL265
Hole/Tab
Slide TL265
into slots
AUDIO/DEFAULT
DSC
UA557
Hardware Default
Jumper
AUDIO/DEFAULT
TL265
Network Link
(Yellow LED)
USER ACTION