Never connect an unregulated gas cylinder to the heater.
Disconnect the gas cylinder when the heater is not use.

LEAK TESTING

Gas connections on the heater are leak tested at the factory prior to ship-
ment. A complete gas tightness check must be performed at the installation
site due to possible mishandling in shipment and/or installation or because
of excessive pressure being applied to the heater. The heater must be chec-
kedwith a full cylinder.
1. Make sure the safety control valve is in the OFF position.
2. Make a soapy water solution of one part liquid detergent and one part
water. The soapy water solution can be applied with a spray bottle, brush or
rag to all gas connections. Soap bubbles will appear in case of a Ieak.
WARNING: Never leak test while smoking!
WARNING: In the event of gas leakage, the appliance shall not be used or if
alight, the gas supply shall be shut off and the appliance shall be investigated
and rectified before it is used again.
3. Turn the gas supply ON. And check all the connections with the soapy
water solution. No bubbles may appear!
4. In case of a leak, turn off the gas supply. Tighten any leaking fittings, then
turn the gas supply ON and recheck. Contact your dealer or gas supplier for
assistance if bubbles continue to appear.
DIAGRAMMATICAL REPRESENTATIONS OF OUTDOOR AREAS
Both ends open
SPECIFICATIONS
Max.Wattage:
Min. Wattage:
Gas Consumption:
Height:
Weight:
Open
Open side must be >25%
of total wall area
13 kW
5 kW
450 g/hr-945 g/hr
227 cm including stand
25 kg
>30% of Total wall area
to be open and unrestricted