Fault code 2A is displayed on the
on LCD and the alarm is
continuously sounding.
Fault code 45 is displayed on the on
the LCD display and the alarm is
continuously sounding.
5. Storage and Maintenance
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C
ambient temperature) has been exceeded, the batteries must be replaced. Contact your reseller
Be sure to deliver the spent battery to a recycling facility or ship it to your dealer
in the replacement battery packing material.
Storage
Prior to storing, charge the UPS for 5 hours. Store the UPS covered and upright in a cool,
dry location. To protect battery performance and limit degradation, recharge the battery in
accordance with the following table:
Storage Temperature
-25°C - 40°C
40°C - 45°C
6. Specifications
MODEL (VPN)
CAPACITY*
INPUT
Low Line Transfer
Low Line
Voltage
Comeback
Range
High Line Transfer
High Line
Comeback
Frequency Range
Phase
Power Factor
THDI
OUTPUT
Output voltage
AC Voltage Regulation
A short circuit of the
charger output has
occurred.
No charger output and
battery voltage is less than
10V/PC.
Recharge Frequency
Every 3 months
Every 2 months
160VAC/140VAC/120VAC/110VAC ± 5 %
(based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
175VAC/155VAC/135VAC/125VAC ± 5 %
THDU < 1.6% @ input and full linear load condition
200/208/220/230/240 VAC
17
Check the wiring of a
connected external battery
pack for short-circuited
Contact your reseller or
Charging Duration
1-2 hours
1-2 hours
UPS2URM3000DC-NC-1E
3000VA / 3000W
300 VAC ± 5 %
290 VAC ± 5 %
40Hz ~ 70 Hz
Single phase with ground
≧ 0.99 @ full load
≦ 5% @ 160-265 VAC
± 1% (Batt. Mode)
**