Mounting
Insulating plate, Cat. No. IPXXX
Mounting of insulating plate IPXXX, (shown shaded in the diagram)
is required on UL/CSA labeled models for all installations in which the Line Voltage exceeds 480 V.
Mount as shown in diagram.
4 x M4 x 85/20
3
Z 2
1.7 Nm
(15 lb-in)
NZM.2-...
35 mm (1.4")
NZM.2-4-...
70 mm (2.8")
10/10
EU: Eaton Industries (Austria) GmbH, Eugenia 1, 3943 Schrems, Austria
UK: Eaton Electric Ltd., P.O. Box 554, Abbey Park, Southampton Road, Titchfield, PO14 4QA, United Kingdom
Wiring terminations circuit breaker type NZM...2...-NA (CNA)
Wiring terminations molded case switch type N(S)2...-NA
Connector
Type
NZM4-XKC
NZM4-XKA
1) NZM4-XKS
2) Integrated
Auxiliary
Terminal
1) Connector Pads Type NZM2-XKS for Compression Crimp lugs supplied standard on all NZM2
circuit breakers and switches.
2) Integrated Auxiliary Terminal on Barrel (Tunnel) Mechanical lug Connector Type NZM2-XKA only.
4 x M4 x 85/20
1.7 Nm
(15 lb-in)
2
2
NZM...2...-NA
> 480 V:
NZM...2...-CNA
1
N(S)2...-NA
Wire size
Wire
75° C
1 x AWG 12 - 350 kcmil
Cu only
1 x AWG 6 - 350 kcmil
Cu only
1 x AWG 12 - 350 kcmil
Cu only
1 x AWG 12 - 18
Cu only
USA:
Eaton.com/contacts
Eaton.com/eatoncare
Eaton.com/aftersales
:MA
+1 877-386-2273
Eaton.com/documentation
Max.
Tightening-
A-Rating
Torque
250
14 Nm (124 lb-in)
5 Nm (44 lb-in)
(AWG10)
250
30 Nm (265 lb-in)
250
14 Nm (124 lb-in)
1.2 Nm (11 lb-in)
© 2002 Eaton Industries (Austria) GmbH
08/22 IL01206006Z
Eaton.com/recycling