Terminations
1/L1,3/L2,5/L3,2/T1,4/T2,6/T3
HLR20/3...
a = 12 mm (0.47")
a
2 x 2.5 - 6.0 mm
(2 x 14 - 10 AWG)
2 x 1.0 - 2.5 mm
(2 x 18 - 14 AWG)
2 x 2.5 - 4.0 mm
(2 x 14 - 12 AWG)
2 x 1.0 - 2.5 mm
(2 x 18 - 14 AWG)
2 x 2.5 - 6.0 mm
(2 x 14 - 10 AWG)
M4, Posidriv 2
UL: 2.0 Nm (17.7 lb-in)
IEC: 1.5 - 2.0 Nm (13.3 - 17.7 lb-in)
→
Use 75 °C copper (Cu) conductors
A1(+), A2( - )
HLR.../3...
a
8 mm (0.31")
2 x 0.5 - 2.5 mm
(2 x 18 - 12 AWG)
2 x 0.5 - 2.5 mm
(2 x 18 - 12 AWG)
M3, Posidriv 1
UL: 0.5 Nm (4.4 lb-in)
IEC: 0.5 - 0.6 Nm (4.4 - 5.3 lb-in)
→
Use 60/75 °C copper (Cu) conductors
UL508
I
[kA
cc max
rms
HLR20/3
100
HLR30/3
100
2/2
EU: Eaton Industries GmbH, Hein-Moeller-Straße 7-11, 53115 Bonn, Germany
UK: Eaton Electric Ltd., P.O. Box 554, Abbey Park, Southampton Road, Titchfield, PO14 4QA, United Kingdom
HLR20/3...
a = 12 mm (0.47")
2
1 x 2.5 - 6.0 mm
(1 x 14 - 10 AWG)
2
1 x 1.0 - 4.0 mm
(1 x 18 - 12 AWG)
2
2
1 x 1.0 - 6.0 mm
(1 x 18 - 10 AWG)
2
M4, Posidriv 2
UL: 2.0 Nm (17.7 lb-in)
IEC: 1.5 - 2.0 Nm (13.3 - 17.7 lb-in)
HLR.../3...
8 mm (0.31")
2
1 x 0.5 - 2.5 mm
(1 x 18 - 12 AWG)
2
1 x 0.5 - 2.5 mm
(1 x 18 - 12 AWG)
M3, Posidriv 1
UL: 0.5 Nm (4.4 lb-in)
IEC: 0.5 - 0.6 Nm (4.4 - 5.3 lb-in)
]
max. size [A]
Class
30
J or CC
40
J
HLR30/3...
UL: a = 11 mm (0.43")
IEC: a = 12 mm (0.47")
2
1 x 2.5 - 25 mm
(1 x 14 - 3 AWG)
2
1 x 2.5 - 16 mm
(1 x 14 - 6 AWG)
2
1 x 4.0 - 25 mm
(1 x 12 - 3 AWG)
M5, Posidriv 2
UL: 2.5 Nm (22 lb-in)
IEC: 2.5 - 3.0 Nm (22 - 26.6 lb-in)
2
2
Voltage [V AC]
max. 600
max. 600
USA:
Eaton.com/eatoncare
+1 877-386-2273
2
2
2
© 2021 Eaton Industries GmbH
Eaton.com/contacts
Eaton.com/aftersales
Eaton.com/recycling
Eaton.com/documentation
09/21 IL034110ZU