English
Introduction
This document is intended for experienced engineers who are
familiar with PAC products and health and safety considerations.
Additional information on software installation and operation is
given in the documentation and help files provided with the
administration software.
All similar controllers on the system should have the
same firmware version number.
A firmware download to the new controller may be required, see
the help file for further details.
Tamper and Override Terminal (NC)
Before powering up, use a short piece of cable to link:
tamper (TAMP) and 0V terminals.
l
override (OVERRIDE) and 0V terminals.
l
Override can be configured for EOL operation if required.
RS-485 Connection
When shielded cables are used, connect the shield on one
controller to the earth terminal labelled "SHIELD".
Only the first and last controllers in the chain, must
have the RS-485 dipswitch set to "IN".
RS-485 LED
RED
The controller is transmitting data
Another controller is transmitting data on the
GREEN
network
Lock EMF Suppression
All locks must be fitted with a means of suppressing back EMF
('spikes'), which are generated by most electric releases, especially
magnetic locks.
All readers and controllers supplied by PAC are supplied with a
Metal Oxide Varistor (MOV).
For currents >1A use the large MOV supplied with the controller.
For currents <1A use the small MOV supplied with the reader.
The MOV will prevent the controller from suffering long term
damage.
Whenever possible this device should be fitted across the lock
terminals. If for any reason the lock terminals are inaccessible, the
MOV may be fitted across the lock output.
The lock relays are protected by a 3A circuit breaker in line with
the RELAY COM connection. These will automatically be reset
when the overload has been removed; both lock outputs are
independent.
Description
- 4 -
Legend for Wiring Diagram on page 3
1
RS-485 connection
2
Dipswitch settings
1. RS-485 termination (IN or OUT, default = OUT)
2. Reader voltage selector (12/24V or 5V, default =
12/24V)
3
RS485 status LEDs
4
RS-232 status LEDs
5
Door 1 LEDs
6
Reader
SIGA/SIGB
0V (sounder)
0V (tamper/DC - door
contact)
7
Request to Exit (NO)
8
Door Contact
9
Lock wiring options:
FAIL SAFE—connect to NC
l
FAIL SECURE—connect to NO
l
10
Door 2 LEDs
11
Serial Number and Barcode
12
One-Touch™ button
13
System status LED
14
Power Access
15
Battery Backup
16
12V/24V Power Supply Unit
MSTAT
(Battery) +
(Battery) -
EARTH
17
PC RS-232 or Ethernet connection
18
Cover Tamper Switch (NC)
19
Door Override (NC)
Removal of short will operate lock relay
l
NOT rated for use as a FIRE OVERRIDE
l
20
Wiegand Reader
** Refer to manufacturer's guide for 3rd-party PSU
+V
1 Red
LED
2 Brown
3 White
0V
4 Black
5 Yellow
6 Blue
1 Blue
RTE
2 Black
0V
PAC Wiring ONLY **
VIN
1 Orange
0V
2 White
3 Pink
4 Red
5 Black
6 Green/Yellow